Reinhäuser VACUTAP® VM® On-Load Tap-Changer Product Leaflet

Reinhäuser VACUTAP® VM® is a versatile vacuum on-load tap-changer for grid and industrial use, with 300,000 maintenance-free operations and 1.2 million…


Reinhäuser VACUTAP® VM® On-Load Tap-Changer Product Leaflet - cover page
Brand
Reinhäuser
Document type
Product Leaflet
Language
English
Pages
10
File format
PDF
File size
835 KB
Published
23 November, 2026
Updated
23 November, 2026
MD5 checksum
037A1325211597BDE225ED5A49716CFF

About this manual

The VACUTAP® VM® is a vacuum-based on-load tap-changer designed for long-term reliability in grid and industrial applications. It combines proven oil technology with vacuum switching, offering 300,000 maintenance-free operations and a 1.2 million operation lifespan. Compatible with OILTAP® M, it enables easy retrofitting. It supports 30-200 MVA transformers and 110-230 kV grids, and is suitable for demanding applications like arc furnaces and HVDC. Features include arc control, step protection, ATEX certification, and earthquake resilience.

What's inside

  • VACUTAP® VM® Overview
  • Vacuum Technology and Compatibility
  • Arc Control System®
  • Step Protection System®
  • Technical Specifications
  • Installation and Retrofitting
  • Certifications and Applications

Specifications

Rated insulation level72.5 kV to 300 kV
Maintenance interval300,000 tap-change operations
Expected service life1.2 million tap-change operations
Max. rated through-current300 A to 1500 A
Rated short-time current4 kA to 15 kA
Rated peak withstand current10 kA to 37.5 kA
Step capacity990 kVA to 3500 kVA
Rated frequency50...60 Hz
Operating positionsmax. 18 to max. 35

Frequently asked questions

What is the maintenance interval for the VACUTAP® VM®?

The maintenance interval is 300,000 tap-change operations without any time limit.

What is the expected service life of the diverter switch insert?

The expected service life is 1.2 million tap-change operations.

Is the VACUTAP® VM® compatible with OILTAP® M?

Yes, it is 100% connection compatible with OILTAP® M and can be retrofitted.

What applications is the VACUTAP® VM® suitable for?

It is suitable for 30-200 MVA transformers and 110-230 kV grids, as well as electric arc furnaces, HVDC, electrolysis, rectifiers, and phase shifters.