The RCI 10-5 Series is a Class 2 Power Limited power supply with charging, intended for use in a controlled environment. It provides universal AC input from 120-240 VAC and field-selectable 12VDC or 24VDC output via a slide switch.

The manual includes installation instructions, input and output specifications, battery backup and supervision relay details, environmental ratings, maintenance recommendations, and a troubleshooting guide for AC and DC LED indications.

What's inside

  • Base Features
  • Installation Instructions
  • Specifications
  • Troubleshooting Guide
  • Maintenance
  • Environmental
  • Supervision
  • Battery Backup

Specifications

AC input voltage120VAC/60Hz or 240VAC/50Hz, automatic switching
Nominal output voltage12VDC or 24VDC
Typical output at 12VDC10.4-13.7VDC, 5A
Supply current at 12VDC5 Amps
Supply current at 24VDC3 Amps
Output protectionClass II Power limited thermally protected DC output
Battery standby5Amps @ 1 hour using 7.5Ah battery(s)
Average recharge current735ma
AC fail relay outputForm C, 2A @ 120VAC
Battery trouble relay outputForm C, 2A @ 120VAC
Operating temperature-0˚C to 49˚C (32˚F to 120˚F)
Usage environmentFor indoor use only

Frequently asked questions

What AC input voltages does the RCI 10-5 power supply accept?

It accepts 120VAC/60Hz or 240VAC/50Hz with automatic switching.

What DC output voltages are available on the RCI 10-5?

The output is field selectable as 12VDC or 24VDC using a slide switch.

Where should the RCI 10-5 power supply be mounted?

Mount it in an accessible location using the mounting keyholes in the back of the box, in a controlled environment.

How often should the battery be replaced if backup is critical?

It is recommended to change the battery every 4 years or less.