Assembly and commissioning instructions for the PETER electronic VersiStart II 3 ... 15L soft starter for three-phase motors.
This document is the assembly and commissioning instructions for the PETER electronic VersiStart II 3 ... 15L soft starter. It covers safety notes, conformity, general description, intended use, EC declaration of conformity, block diagram, mounting, power and control connections, LED indicators, parameter settings, technical data, dimensioning rules, and installation guidelines.
The soft starter is suitable for three-phase motors in star or delta connection and changes motor voltage in two phases by phase control. Acceleration time, starting voltage, and deceleration time are separately adjustable, and a boost function can apply an increased starting voltage for 0.5 s. The device is snap-mounted on a 35 mm top-hat rail and is intended for installation in a housing with at least IP54 protection.
| Motor connection | 3-phase motors in star or delta connection |
|---|---|
| Acceleration time | 0.5...10 sec |
| Starting voltage | 0...80% of rated voltage |
| Deceleration time | 0.5...10 sec |
| Boost duration | 0.5 s |
| Overvoltage category | III |
| Pollution degree | 2 or better |
| Enclosure rating | IP54 minimum housing |
| Mounting rail | 35 mm top-hat rail |
| Minimum clearance | 40 mm |
It is suitable for the operation of three-phase motors in star or delta connection.
It is switched on by bridging terminals X6 and X7, applying an increased starting voltage at the beginning of the soft start.
The start time potentiometer is at mid-position, while the initial torque and stop time potentiometers are at the left stop.
When the contact on terminals X5 and X6 is closed, the motor accelerates; when it is open, the motor decelerates.