Pensotti Classic ASME non-condensing boiler troubleshooting manual covering error codes, reset methods, LCD blank diagnosis, and domestic hot water sensor…
This Pensotti Classic boiler troubleshooting manual covers all models of the ASME non-condensing Classic boiler line. It explains how to retrieve error code history using the INFO button, lists error codes with their reset methods, and provides step-by-step procedures for diagnosing a blank LCD display.
Additional sections cover dedicated electrical circuit and earth ground requirements, minimum and maximum fire gas pressure adjustment, diverter valve operation, domestic hot water flow switch and sensor operation, and domestic hot water production capability calculations for PNCC models.
| D.H.W. sensor resistance at 77°F | 9,999 Ohms |
|---|---|
| MPCB fuse rating | 4 Amp |
| Boiler supply voltage | 120V |
Turn the boiler off using the Mode Selection button, press and hold the INFO button for several seconds, then scroll through the last five error codes using the heat temperature + and - buttons.
E04 indicates low water pressure in the heating circuit and resets automatically upon repair.
A 10K NTC thermistor has 9,999 Ohms of resistance at 77 degrees F.