Installation and troubleshooting guide for the NY Thermal Sentry 2100 T2.2 boiler controller, covering menu settings, compatibility, and error codes.
This document provides installation instructions for the NY Thermal Sentry 2100 T2.2 controller, specifically for use with Trinity boiler models such as the T150, T200, and Ti series. It details the specific menu options available, including set points for domestic hot water and central heating, as well as gas input values and safety features like freeze protection.
| Compatible Boiler Models | T150, T150C, T200, T200C, Ti100, Ti150, Ti150C, Ti200, Ti200C |
|---|---|
| Document Part Number | 82013 |
| Version Date | 2011-07-21 |
| Good Fuse Resistance | 300-400 Ohms |
| Blown Fuse Resistance | OL (Open) |
No, the Sentry control version T2.2 cannot be used on Trinity boiler model Ti400 or any non-Trinity boiler models.
The typical setting for the DHW Set Point is 160ºF.
ER1 indicates that the Sentry has sensed a water temperature in excess of 250ºF at the Water Sensor.
The controller locks up due to excessive noise, current, or voltage spikes in the 120V power supply.