nVent ERICO UTB Series Data and Signal Line Protection

nVent ERICO UTB transient barriers protect data, signalling and control circuits, with selection guidance, applications and specifications.


nVent ERICO UTB Series Data and Signal Line Protection - cover page
Brand
nVent ERICO
Category
Other Electronics
Document type
Product Leaflet
Language
English
Pages
12
File format
PDF
File size
2.6 MB
Published
13 November, 2026
Updated
13 November, 2026
MD5 checksum
251A632BB8CD69D25C43AFD7B59CA38B

About this manual

The UTB series is designed to provide transient protection for equipment from surges induced onto balanced pair signal lines or low-voltage AC or DC power supplies. It is well suited to industrial equipment such as PLCs and SCADA systems, fire and security alarms, and industrial monitoring and control equipment.

The leaflet explains where to install surge protection, how to select an SPD using five parameters, and sample applications. UTB single-pair and dual-pair barriers feature multi-stage protection, common-mode and differential-mode protection, hot-swappable plug-and-base construction, and a 20 kA 8/20 µs surge rating.

What's inside

  • How to Select Surge Protection for Data, Signalling and Control Circuits
  • Where should the SPD(s) be installed?
  • How to select an SPD for a given location
  • Sample Applications
  • UTB SP & SPG Universal Transient Barrier Single Pair
  • UTB DP Universal Transient Barrier Dual Pair

Specifications

Nominal Voltage0 V to 3 VAC / 0 V to 5 VDC (UTB5SP)
Max Continuous Operating Voltage5 VAC / 7 VDC (UTB5SP)
Max Line Current2 A
Frequency0.5 MHz (UTB5SP)
Loop Resistance1.0 Ω
Max Discharge Current20 kA 8/20 µs
Protection ModesDifferential and common mode
TechnologyGDT, MOV, silicon
Voltage Protection Level (8/20 µs), L-L10 V @ 3 kA (UTB5SP)
Dimensions (H x D x W)90 x 72 x 12 mm (3.54 x 2.83 x 0.47 in)
Weight0.07 kg (0.15 lbs)
EnclosureDIN 43 880, UL94V-0 thermoplastic, IP 20 (NEMA-1)
Connection1 mm² to 2.5 mm² (#18 AWG to 14 AWG)
Mounting35 mm top hat DIN rail
Operating Temperature-20°C to 65°C (-4°F to 149°F)
Humidity0% RH to 90% RH
ApprovalsCE, UL 497B
Surge Rating20 kA 8/20 µs

Frequently asked questions

Where should SPDs be installed for communication or signal lines entering or exiting a building?

They should be installed at the point-of-entry or at the equipment termination itself.

What surge rating is generally sufficient for circuits internal to a building?

Surge ratings of 1-5 kA are generally sufficient.

How should the SPD clamping voltage be selected?

It should be selected to be approximately 20% higher than the peak working voltage of the circuit.

What is the maximum discharge current rating of the UTB single-pair barriers?

The maximum discharge current is 20 kA 8/20 µs.