nVent ERICO UTB transient barriers protect data, signalling and control circuits, with selection guidance, applications and specifications.
The UTB series is designed to provide transient protection for equipment from surges induced onto balanced pair signal lines or low-voltage AC or DC power supplies. It is well suited to industrial equipment such as PLCs and SCADA systems, fire and security alarms, and industrial monitoring and control equipment.
The leaflet explains where to install surge protection, how to select an SPD using five parameters, and sample applications. UTB single-pair and dual-pair barriers feature multi-stage protection, common-mode and differential-mode protection, hot-swappable plug-and-base construction, and a 20 kA 8/20 µs surge rating.
| Nominal Voltage | 0 V to 3 VAC / 0 V to 5 VDC (UTB5SP) |
|---|---|
| Max Continuous Operating Voltage | 5 VAC / 7 VDC (UTB5SP) |
| Max Line Current | 2 A |
| Frequency | 0.5 MHz (UTB5SP) |
| Loop Resistance | 1.0 Ω |
| Max Discharge Current | 20 kA 8/20 µs |
| Protection Modes | Differential and common mode |
| Technology | GDT, MOV, silicon |
| Voltage Protection Level (8/20 µs), L-L | 10 V @ 3 kA (UTB5SP) |
| Dimensions (H x D x W) | 90 x 72 x 12 mm (3.54 x 2.83 x 0.47 in) |
| Weight | 0.07 kg (0.15 lbs) |
| Enclosure | DIN 43 880, UL94V-0 thermoplastic, IP 20 (NEMA-1) |
| Connection | 1 mm² to 2.5 mm² (#18 AWG to 14 AWG) |
| Mounting | 35 mm top hat DIN rail |
| Operating Temperature | -20°C to 65°C (-4°F to 149°F) |
| Humidity | 0% RH to 90% RH |
| Approvals | CE, UL 497B |
| Surge Rating | 20 kA 8/20 µs |
They should be installed at the point-of-entry or at the equipment termination itself.
Surge ratings of 1-5 kA are generally sufficient.
It should be selected to be approximately 20% higher than the peak working voltage of the circuit.
The maximum discharge current is 20 kA 8/20 µs.