Nuvia Self-Cleaning Filter instruction manual covering installation, startup, use, maintenance, and troubleshooting.
Nuvia self-cleaning filter instruction manual covers product identification, precautions, installation, startup, use, maintenance, and troubleshooting. It states default maximum working pressure and temperature when the product label is missing or illegible.
Routine maintenance is back-wash cleaning in counter-current operation, with extraordinary cartridge cleaning and replacement intervals for plastic net cartridges, stainless steel net cartridges, and the housing bowl.
| Default maximum working pressure | 116 psi (8 bar) |
|---|---|
| Default maximum working temperature | 113°F (45°C) |
| Hot water filter maximum temperature | 176°F (80°C) |
| Brass/metal head maximum working pressure | 145 psi (10 bar) |
| Minimum supply pressure for back-wash | 26 psi (1.8 bar) |
| Drain tube maximum length | 2 metres |
| Plastic net cartridge replacement interval | At least every 24 months |
| Stainless steel net cartridge replacement interval | At least every 48 months |
| Housing bowl replacement interval | At least every 5 years |
Max pressure is 116 psi (8 bar) and max temperature is 113°F (45°C), except hot water filters up to 176°F (80°C) and brass/metal head filters up to 145 psi (10 bar).
The rubber tube must not be more than 2 metres long.
Back-wash cleaning occurs in excellent conditions with minimum 26 psi (1.8 bar) supply pressure.
Replace plastic net cartridges at least every 24 months, stainless steel net cartridges at least every 48 months, and the housing bowl at least every 5 years.