The Notifier FST-851(A) Series Intelligent Thermal Detectors are advanced fire detection devices that offer fixed-temperature and rate-of-rise thermal detection in a low-profile design. They utilize an innovative thermistor sensing circuit and are compatible with Notifier Onyx and CLIP series Fire Alarm Control Panels via the FlashScan communication protocol.

These detectors are available in different models, including the standard FST-851(A) with a factory preset fixed temperature of 135°F (57°C), the rate-of-rise model FST-851R(A), and the high-temperature model FST-851H(A) set at 190°F (88°C). The series features addressable capabilities, integral communication, and various mounting options including separate bases for photoelectric, ionization, and thermal sensors.

What's inside

  • Features
  • Specifications
  • Applications
  • Installation
  • Agency Listings and Approvals
  • Product Line Information
  • Intelligent Bases
  • Accessories

Specifications

Fixed-temperature setpoint135°F (57°C)
Rate-of-rise detection15°F (8.3°C) per minute
High-temperature setpoint190°F (88°C)
Operating temperature range-20°C to 38°C (–4°F to 100°F)
Voltage range15 - 32 volts DC peak
Standby current300 µA @ 24 VDC
Detector spacing (UL)50 ft. (15.24 m) center to center

Frequently asked questions

What is the fixed temperature setpoint for the FST-851(A) model?

The factory preset fixed temperature is 135°F (57°C).

What is the rate-of-rise detection threshold?

The rate-of-rise model detects a rise of 15°F (8.3°C) per minute.