The NJ39 DTU intelligent IoT circuit breaker operation manual covers features, parameters, operating conditions, and button instructions for systems up to…
The NJ39 DTU is an intelligent IoT molded case circuit breaker for power systems with a rated working voltage of 400 V AC, 50 Hz, and rated current of 800 A or below. It provides measurement and protection for voltage, current, residual current, cable temperature, power consumption, power, and power factor, and supports GPRS wireless communication and mobile APP remote monitoring.
This operation manual describes product dimensions, protection, display, setting, control, self-test, and monitoring functions. It also lists normal operating conditions, controller performance indicators, tripping characteristics, and button and external terminal operating instructions. This manual is written in Chinese.
| Rated working voltage | 400 V AC |
|---|---|
| Frequency | 50 Hz |
| Rated current | 800 A or below |
| Overvoltage operating value | 285±5 V (default) |
| Undervoltage operating value | 165±5 V (default) |
| Phase loss operating value | 120±5 V (default) |
| Ambient temperature | -30°C to +70°C |
| Altitude | Not exceeding 2000 m |
It uses GPRS wireless communication to send data to the cloud and enables mobile APP interconnection and remote monitoring.
The default overvoltage operating value is 285±5 V and can be set by the user.
The ambient temperature range is -30°C to +70°C.