NARI-RELAYS RCS-943AU High-Voltage Transmission Line Protection Device Technical and User Manual

Technical and user manual for the NARI-RELAYS RCS-943AU high‑voltage transmission line protection device.


NARI-RELAYS RCS-943AU High-Voltage Transmission Line Protection Device Technical and User Manual - cover page
Brand
NARI-RELAYS
Category
Industrial Supply
Document type
User Manual
Language
Chinese
Pages
59
File format
PDF
File size
830 KB
Updated
28 September, 2026
MD5 checksum
1987BE671F620C3CE6E90F538B327D13

About this manual

This manual documents the NARI-RELAYS RCS-943AU digital high-voltage transmission line protection device, intended for main and backup protection of 110 kV lines requiring low-frequency and undervoltage tripping. It covers protection configuration, technical parameters, software operating principles, hardware structure, settings and commissioning.

The document also explains panel layout, terminals, output contacts, indicator lights, LCD menus, device operation, test procedures, channel commissioning and fiber-optic connection notes. It applies to the RCS-943AUV2.** program version. This manual is written in Chinese.

What's inside

  • Overview and application scope
  • Protection configuration and performance features
  • Mechanical, environmental and electrical parameters
  • Software operating principles
  • Hardware structure, panel and terminals
  • Settings and commissioning notes
  • Operation, indicators and LCD menus
  • Commissioning outline and test procedures
  • Channel and fiber-optic commissioning

Specifications

Chassis dimensions482 mm × 177 mm × 291 mm; embedded installation
Normal operating temperature0 to 40 °C
DC power supply220 V, 110 V; tolerance +15% / -20%
AC voltage3/100 (rated voltage Un)
AC current5 A, 1 A (rated current In)
Frequency50 Hz / 60 Hz
Differential protection full-line trip timeLess than 25 ms (differential current greater than 1.5 times high differential setting)
Distance protection Zone I trip timeLess than 30 ms
Distance protection setting range0.01–40 Ω (In=5 A); 0.05–200 Ω (In=1 A)
Low-frequency protection setting range45 Hz to 50 Hz
Undervoltage protection setting range60 V to 100 V
Stored action reportsLatest 64 action reports
Stored fault recording reports24 fault recording reports
Communication protocolsDL/T667-1999 (IEC 60870-5-103) or LFP (V2.0)
Fiber optic type and wavelengthSingle-mode CCITT Rec.G652, 1310 nm
Fiber optic transmission distanceLess than 100 km at 64 kbit/s; less than 60 km at 2048 kbit/s
Channel delay requirementLess than 15 ms one-way transmission

Frequently asked questions

What is the RCS-943AU protection device used for?

It is a microprocessor-based digital transmission line fast protection device used as main and backup protection for 110 kV lines requiring low-frequency and undervoltage tripping.

What protection functions does the RCS-943AU include?

It includes phase-segregated and zero-sequence current differential fast main protection, three-stage phase and ground distance protection, four-stage zero-sequence directional overcurrent backup protection, and low-frequency and undervoltage tripping functions.

What are the DC power supply ratings?

The device accepts 220 V and 110 V DC power supplies with an allowable deviation of +15% and -20%.

Which communication interfaces are provided?

Options include RS-485 or Ethernet interfaces, an RS-485 twisted-pair interface for GPS time synchronization, a printer interface, and a front-panel RS-232 debugging interface.

What is the required channel delay for protection communications?

One-way transmission delay must be less than 15 ms, and the transmit and receive routes must have consistent delay.

Download PDF (830 KB)