Manual for the Nanhu Electric JDZX9-35 single-phase fully enclosed semi-insulated cast voltage transformer for 35 kV and below systems.
The JDZX9-35 is a single-phase, fully enclosed, semi-insulated cast voltage transformer for indoor use in power systems with rated frequency 50 Hz or 60 Hz and rated voltage up to 35 kV. It is intended for energy metering, voltage monitoring, and relay protection.
The manual covers model meaning, operating conditions, main performance parameters, insulation requirements, temperature rise limits, short-circuit withstand capability, acceptance, installation, use, maintenance, storage, random documents, and outline and installation dimensions. This manual is written in Chinese.
| Rated voltage ratio | 35/√3/0.1/√3/0.1/3 kV |
|---|---|
| Rated frequency | 50 Hz |
| Highest working voltage | 40.5 kV |
| Secondary winding rated voltage | 0.1/√3 kV |
| Secondary rated burden and accuracy class | 30 VA / 100 VA, 0.2 / 6P class |
| Limit secondary burden | 600 VA |
| Rated voltage factor | 1.2 continuous |
| Ambient temperature | Maximum 65 C, minimum -45 C, daily average 40 C |
| Altitude | Not more than 1000 m |
| Lightning impulse withstand voltage (full wave) | 200 kV peak |
| Lightning impulse withstand voltage (chopped wave) | 230 kV peak |
| Power-frequency withstand voltage | 3 kV for 1 min |
| Frequency-doubled induced withstand voltage | 80 kV for 40 s |
| Partial discharge level | Not more than 20 pC |
| Temperature rise limit | Not more than 75 K |
| Short-circuit withstand | 1 s external short circuit |
| Ratio error (0.2 class) | ±0.16% |
The rated frequency is 50 Hz.
The highest working voltage is 40.5 kV.
The winding temperature rise must not exceed 75 K.
The supplied documents include a packing list, certificate, factory test record, and product instruction manual.