The NA1523(v2.0) smart controller user manual provides setup, operation, temperature control, defrosting, alarm handling, and technical specifications.
This manual explains how to configure and operate the NA1523 smart controller, covering temperature and temperature‑difference settings, defrost cycle adjustment, manual defrost, alarm management, and advanced internal parameter adjustments for professional users.
It also lists the main functions, technical specifications such as temperature range, power supply, output contact capacity, and wiring guidelines, along with safety precautions for installation and use. This manual is written in Chinese.
| Temperature display range | -50 °C to 125 °C (0.1 °C steps) |
|---|---|
| Defrost cycle range | 0 h to 99 h, adjustable |
| Temperature setting range | -45 °C to 120 °C, adjustable |
| Power supply voltage | 9 V to 12 V AC |
| Output contact capacity | 2 A / 380 V |
| Opening size | 106.3 mm × 165 mm (H × W) |
| Temperature sensor type | NTC R25=5kΩ, B(25/50)=3470 K |
| Operating environment | Temperature -10 °C to 45 °C, humidity ≤85 %, no condensation |
Long‑press the “Select” key for 2 seconds to enter setting mode, then use the “+” or “–” keys to adjust the temperature or temperature‑difference values.
Set the defrost cycle to 0 hours; the controller will then treat the defrost probe as a normal temperature sensor.
Press any key on the controller while the alarm is sounding to mute it.