Installation and operation manual for the Multispan MFM 1 3-M1 Multi Function Meter, covering mechanical setup, wiring, parameter configuration, and MODBUS…
This manual provides mechanical installation guidelines for the Multispan MFM 1 3-M1 Multi Function Meter, including panel cut-out dimensions, terminal block wiring, and safety precautions. It details the environmental conditions and power supply requirements necessary for proper installation.
| Operating Temperature | 0°C to 55°C |
|---|---|
| Protection Level | IP-65 (Front side) |
| Accuracy Class | Class 0.5 (Standard) |
| Power Consumption | Approx 4 VA @ 230V AC MAX |
| Supply Voltage | 100 to 270V AC, 50/60Hz |
| Display | 4 Digit, 3 Line 0.5 7" RED |
| Panel Cut out Dimension | 96 (H) x 96 (W) x 54 (D) mm |
| Communication | RS-485 MODBUS |
The tightening torque for the terminal block screws should be in the range of 1.2 N.m.
No, do not use isopropyl alcohol or any other cleaning agent to clean the equipment.
The primary CT rating is programmable up to 6000A.
The available baud rates are 4800, 9600, 19200, and 38400 bps.