Mindman MAER200/300 Series Electro-Pneumatic Regulator Service Manual

This service manual covers the operation, wiring, setting, and error indication functions of the Mindman MAER200/300 series electro-pneumatic regulators.


Mindman MAER200/300 Series Electro-Pneumatic Regulator Service Manual - cover page
Brand
Mindman
Category
Industrial Supply
Document type
Service Manual
Language
Chinese
Pages
16
File format
PDF
File size
1.1 MB
Published
13 November, 2026
Updated
13 November, 2026
MD5 checksum
22F05775395FD95F4BA4D86328DDCB51

About this manual

The Mindman MAER200/300 series electro-pneumatic regulator is designed for controlling pressure in pneumatic systems. The manual provides detailed specifications for various port sizes, pressure ranges, and signal types, including current (4~20mA) and voltage (0~10V/0~5V) inputs. It outlines the necessary precautions for safe operation, such as avoiding direct sunlight, ensuring clean compressed air, and preventing input signals from exceeding specifications to avoid malfunction or fire hazards.

The document details the wiring methods for power supply, input signals, and monitor outputs, specifying wire colors and connector types. It also explains the professional setting mode for adjusting parameters like minimum and maximum pressure, gain, sensitivity, and energizing time. Additionally, it describes the error indicating function, which displays codes like Er1 (Input signal exceeds specification) and Er6 (Over current errors) to assist in troubleshooting. This manual is written in Chinese.

What's inside

  • Precaution
  • Wiring method
  • Setting method
  • Error indicating function
  • Key locking function
  • Display Symbols description
  • Application of proportional pressure controls

Specifications

Input Signal TypeCurrent DC4~20mA, Voltage DC0~10V, Voltage DC0~5V
Analog Output TypeDC1~5V, DC4~20mA (Source type)
Preset Input UnitMPa, kgf/cm2, bar, psi, kPa
Port Size Options1/4, 3/8, 1/2
Pressure Range Options0.1 MPa, 0.5 MPa, 0.9 MPa
Maximum Current Load125mA

Frequently asked questions

What happens if the input signal exceeds the specification?

The product could malfunction or catch fire if voltage exceeding the working range is applied.

What does error code Er1 indicate?

Er1 indicates that the input signal exceeds the specification.

What does error code Er6 indicate?

Er6 indicates an over current error in the switch output, typically when the current is approx. 125mA or more.