This manual provides installation, connection, and maintenance instructions for the MG EM-8119 Rev.14 surge protector designed for 4-20mA signal lines.
The MG EM-8119 Rev.14 is a lightning surge protector designed specifically for 4-20mA DC and pulse signal lines, including both 4-wire and 2-wire transmitters. It absorbs surge voltages without affecting the instrumentation signal and ensures no interruption of the signal by unplugging the element. The unit features a discharge capacity of 5000 Amps and includes a head element and a base socket. This manual is written in Japanese.
| Max. discharge current (Imax) | 5000A (8 / 20 µs) |
|---|---|
| Max. continuous operating voltage (Uc) | 30V (Line to Line), 70V (Line to Earth) |
| Voltage protection level (Up) @1kV (100A) | 40V (Line to Line), 80V (Line to Earth) |
| Leakage current | ≤ 5µA |
| Capacitance (reference value) @1 MHz | ≤ 2000pF (Line to Line), ≤ 100pF (Line to Earth) |
| Response time | ≤ 4 nsec. (Line to Line), ≤ 20 nsec. (Line to Earth) |
| Internal series resistance | 20Ω ±10% |
| Environmental temperature | -5 to +55°C |
The discharge capacity of this unit has been increased to 5000 Amps.
We recommend checking the surge protector about twice a year, before and after the rainy season.
The required torque for the screw terminal is 0.8 N·m.