This manual describes the RK series variable frequency power supply made by Shenzhen Meiruike Electronic Co., Ltd., a unit that provides a pure sine wave output as a standard AC source. It covers precautions, how to choose the power supply capacity for resistive, inductive, rectifier and mixed loads, the front-panel controls and displays, device specifications, step-by-step operation and troubleshooting of common faults.
The document also explains HI/LO output voltage range switching, fixed and adjustable output frequency settings (45–70 Hz), restarting with the RESET switch after overload or short-circuit protection trips, and an appendix table listing input currents, protection switch ratings, wire sizes and output currents for 220 V single-phase and 380 V three-phase models from 1 kVA to 90 kVA. This manual is written in Chinese.
| Circuit type | IGBT PWM pulse width modulation |
|---|---|
| Output capacity | 0.5 kVA (checked on the RK-5000 specification sheet) |
| Input voltage | Single-phase 2-wire 220 V ±10%, 50 Hz |
| Input frequency | 50 Hz / 60 Hz ±5% |
| Output voltage | 0–300 V continuously adjustable; HI/LO ranges: HI 0–300 V, LO 0–150 V |
| Output frequency | Fixed 50 Hz, 60 Hz, 2F/4F, 400 Hz; adjustable 45 Hz–70 Hz |
| Load regulation | ≤0.5% |
| Frequency stability | ≤0.1% |
| Waveform distortion | ≤2% (measured under resistive load) |
| Efficiency | ≥85% at full load |
| Protection | Overload, short-circuit, over-voltage/current, over-temperature protection and buzzer alarm |
| Operating environment | Temperature 0–40 °C, relative humidity 0–90% |
| Display resolution | Voltage 0.1 V, current 0.01 A, frequency 0.1 Hz |
For a resistive load the power supply capacity is 1.1 times the load power.
Check for a short circuit in the load connected to the output, replace a faulty RESET button, or move the unit to a place with better ventilation.
Turn the selector switch to [VAR] and turn the VAR adjustment knob until the frequency display shows 55.
After about 20 seconds the buzzer sounds; press the [RESET] switch on the panel and the output voltage is then supplied.
HI is 0–300 V and LO is 0–150 V; switch off the connected load and the output protection switch before changing the HI/LO selector.