Installation manual for Liberty Pumps 7034000 L LE and LEH Series sewage pumps, covering basin setup, pump installation, electrical service, operation and…
This installation manual covers Liberty Pumps LE40, LE50, LE70, LE100, LEH100, LEH150 and LEH200 Series sewage pumps. It includes model specifications, sealed and vented basin requirements, simplex and duplex pump installation, electrical service and operation, maintenance and troubleshooting, and warranty information.
The manual lists model data such as horsepower, voltage, phase, full load amps, solids handling, discharge size, automatic or manual operation, and shut-off head. It also gives safety warnings for electric shock, grounding, extension cords, protective clothing, and use in flammable or corrosive liquids.
| Minimum basin diameter | 18 in |
|---|---|
| Minimum basin depth | 24 in |
| Minimum pump turn-off level | 6 in |
| Maximum water temperature | 140°F (60°C) |
| Electrical outlet height | At least 4 ft above floor level |
| Minimum application head for LEH100 Series | 15 ft |
| Minimum application head for LEH150 and LEH200 Series | 20 ft |
The basin should have a minimum diameter of 18 inches and a minimum depth of 24 inches.
No. The manual says not to use an extension cord.
Always disconnect the pump from the power source before handling or making adjustments.
Reverse any two of the three power leads, and code the wires for reconnection after installation.