KRON VA/VX/VR AC Voltage Transducer User Manual

User manual for KRON VA, VX and VR AC voltage transducers: technical characteristics, wiring diagrams, analog output, installation and product coding.


KRON VA/VX/VR AC Voltage Transducer User Manual - cover page
Brand
Kron
Category
Converter
Document type
User Manual
Language
Portuguese
Pages
16
File format
PDF
File size
342 KB
Published
08 November, 2026
Updated
08 November, 2026
MD5 checksum
137FBF689DA4A0093C6EEB0F0FB56E0E

About this manual

This is the KRON user manual (revision 4.0, dated 25/02/2016) for the VA, VX and VR AC voltage transducers, which convert alternating voltage signals into DC voltage or current signals that can be read by PLCs and digital indicators, galvanically isolated from the input. The VA and VX models use RMS measurement for systems with undistorted sinusoidal waveforms (VX with expanded scale), while the VR model uses TRUE RMS measurement for distorted waveforms with harmonics up to the 16th order. Single and triple (three transducers in one housing) versions are described.

The manual covers the introduction and warranty terms, the difference between RMS and TRUE-RMS measurement, technical characteristics, product dimensions, wiring diagrams, analog output, installation of the product and Appendix A with the product coding. This manual is written in Portuguese.

What's inside

  • Introdução
  • Termo de Garantia
  • Medição RMS x Medição TRUE-RMS
  • Características Técnicas
  • Dimensional do Produto
  • Esquemas de Ligação
  • Saída Analógica
  • Instalação do Produto
  • Apêndice A: Codificação do Produto

Specifications

Voltage input, nominal values110 Vca, 115 Vca, 150 Vca, 220 Vca, 380 Vca
Effective measuring range10 to 110% of Vn
Short-duration overload1.5 x Vn (1 s)
Continuous overload1.2 x Vn
Input consumptionless than 0.5 VA
Frequency60 or 50 Hz models (measuring range ±5 Hz)
Auxiliary supply, AC110 or 220 Vca (±15%)
Auxiliary supply, DC12, 24, 48, 125 Vcc (±20%)
Maximum supply consumption3.5 VA single model; 10 VA triple model
Operating temperature-10 to 60 °C
Operating humidity0-95% (non-condensing)
Temperature coefficient0.01%/°C
Accuracy0.25% (0.2% on request)
Isolation2 kV (60 Hz, 1 minute)
Impulse test5 kV – 1.2/50 µs – 0.5 J
Output rippleless than 0.5% of full scale
Response timeless than 400 ms in 90% of cases
Degree of protectionIP40 housing, IP00 terminals
Housing and connectionsExtruded aluminum case; M3 screw terminals
StandardNBR 8145

Frequently asked questions

What is the difference between the VA, VX and VR models?

The VA and VX models use RMS measurement for sinusoidal waveforms without harmonic distortion, the VX having an expanded scale, while the VR model uses TRUE RMS measurement for distorted waveforms with harmonics up to the 16th order.

What error can an RMS transducer show on a distorted waveform?

On distorted waveforms, RMS-measuring transducers can show measurement errors of more than 50%, which is why TRUE RMS (VR) models are recommended in those situations.

How long is the KRON warranty?

KRON provides a 1-year warranty from the date of purchase, proven by the purchase invoice, and it does not cover tampered, opened or overloaded units.

How is the transducer installed and protected?

It is fixed to the back of a panel with four screws, and an external 0.250 mA fuse is recommended to protect the auxiliary supply and the voltage inputs.

Download PDF (342 KB)