User manual for KRON VA, VX and VR AC voltage transducers: technical characteristics, wiring diagrams, analog output, installation and product coding.
This is the KRON user manual (revision 4.0, dated 25/02/2016) for the VA, VX and VR AC voltage transducers, which convert alternating voltage signals into DC voltage or current signals that can be read by PLCs and digital indicators, galvanically isolated from the input. The VA and VX models use RMS measurement for systems with undistorted sinusoidal waveforms (VX with expanded scale), while the VR model uses TRUE RMS measurement for distorted waveforms with harmonics up to the 16th order. Single and triple (three transducers in one housing) versions are described.
The manual covers the introduction and warranty terms, the difference between RMS and TRUE-RMS measurement, technical characteristics, product dimensions, wiring diagrams, analog output, installation of the product and Appendix A with the product coding. This manual is written in Portuguese.
| Voltage input, nominal values | 110 Vca, 115 Vca, 150 Vca, 220 Vca, 380 Vca |
|---|---|
| Effective measuring range | 10 to 110% of Vn |
| Short-duration overload | 1.5 x Vn (1 s) |
| Continuous overload | 1.2 x Vn |
| Input consumption | less than 0.5 VA |
| Frequency | 60 or 50 Hz models (measuring range ±5 Hz) |
| Auxiliary supply, AC | 110 or 220 Vca (±15%) |
| Auxiliary supply, DC | 12, 24, 48, 125 Vcc (±20%) |
| Maximum supply consumption | 3.5 VA single model; 10 VA triple model |
| Operating temperature | -10 to 60 °C |
| Operating humidity | 0-95% (non-condensing) |
| Temperature coefficient | 0.01%/°C |
| Accuracy | 0.25% (0.2% on request) |
| Isolation | 2 kV (60 Hz, 1 minute) |
| Impulse test | 5 kV – 1.2/50 µs – 0.5 J |
| Output ripple | less than 0.5% of full scale |
| Response time | less than 400 ms in 90% of cases |
| Degree of protection | IP40 housing, IP00 terminals |
| Housing and connections | Extruded aluminum case; M3 screw terminals |
| Standard | NBR 8145 |
The VA and VX models use RMS measurement for sinusoidal waveforms without harmonic distortion, the VX having an expanded scale, while the VR model uses TRUE RMS measurement for distorted waveforms with harmonics up to the 16th order.
On distorted waveforms, RMS-measuring transducers can show measurement errors of more than 50%, which is why TRUE RMS (VR) models are recommended in those situations.
KRON provides a 1-year warranty from the date of purchase, proven by the purchase invoice, and it does not cover tampered, opened or overloaded units.
It is fixed to the back of a panel with four screws, and an external 0.250 mA fuse is recommended to protect the auxiliary supply and the voltage inputs.