KPS Digital Earth Resistance Tester Instruction Manual

KPS Digital Earth Resistance Tester instruction manual covering safety notes, features, specifications, maintenance, and measurement methods.


KPS Digital Earth Resistance Tester Instruction Manual - cover page
Brand
KPS
Category
Test Set
Document type
User Manual
Language
Spanish
Pages
27
File format
PDF
File size
2.2 MB
Published
06 November, 2026
Updated
06 November, 2026
MD5 checksum
10226DF97D8544CA4969C5D08D666BBF

About this manual

This is the instruction manual for the KPS Digital Earth Resistance Tester, a device used to measure earth resistance in ohms for building grounding installations, server rooms, military facilities, communications installations, and radio and cable towers.

The manual includes safety notes, product features, technical specifications, battery and fuse replacement, cleaning and storage instructions, and methods for measuring earth voltage and earth resistance using two-pole and auxiliary earth spike methods. This manual is written in Spanish.

What's inside

  • Introduction
  • Safety notes
  • Features
  • Specifications
  • Maintenance
  • Measuring methods

Specifications

Earth resistance measuring ranges0-20Ω / 0-200Ω / 0-2000Ω
Earth voltage measuring range0-200 Vac (40-500Hz)
Earth resistance accuracy±(1.5%rdg+2dgt) or ±0.1Ω
Testing frequency820 Hz
Display3½ digit (2000 counts)
Dimensions221(L) × 110(W) × 57(D)mm
Weight with batteriesApprox. 600g
Power supply6 x 1.5V (AA)

Frequently asked questions

What safety standards does the tester meet?

It meets IEC/EN 61010-1 CAT IV 200V, IEC 61557-1, IEC 61557-5, and EN 61326-1.

How are the batteries replaced?

Disconnect the test leads, set the selector to OFF, unscrew the battery cover, replace the AA batteries, and reinstall the cover.

What is the testing frequency?

The testing frequency is 820 Hz.

What are the earth resistance measuring ranges?

The ranges are 0-20Ω, 0-200Ω, and 0-2000Ω.