Jinko Solar JKS-3~6HLVS-ABI Series Hybrid Inverter User Manual

User manual for the Jinko Solar JKS-3~6HLVS-ABI series hybrid inverter, covering installation, commissioning, operation, troubleshooting, and specifications.


Jinko Solar JKS-3~6HLVS-ABI Series Hybrid Inverter User Manual - cover page
Brand
Jinko Solar
Category
inverter
Document type
User Manual
Language
English
Pages
37
File format
PDF
File size
5.4 MB
Published
13 November, 2026
Updated
13 November, 2026
MD5 checksum
22A80D813D73D4575B649125CB501167

About this manual

The JKS-3~6HLVS-ABI series is a hybrid inverter used to store energy generated by photovoltaic cell panels or energy from the grid in a battery; energy can also be sent to the power grid for self-consumption, and the unit can be used as backup power when grid power is lost. The series includes six types: JKS-3HLVS-ABI, JKS-3.6HLVS-ABI, JKS-4HLVS-ABI, JKS-4.6HLVS-ABI, JKS-5HLVS-ABI, and JKS-6HLVS-ABI.

The manual provides product information and installation instructions for professional electrical personnel, including safety instructions, unpacking, installation, grounding, commissioning, display and button operation, communication, country setting, start-up and shutdown, fault removal, decommissioning, and product specifications. It states that the inverter can be used with lithium or lead-acid batteries, and that Jinko can only provide lithium batteries compatible with the inverter.

What's inside

  • Brief Introduction
  • Safety
  • Product Description
  • Installation
  • Commissioning
  • Start-Up and Shut Down
  • Fault Removal
  • Decommissioning
  • Product Specification
  • Certificate

Specifications

Max. PV voltage550 V DC
PV voltage range120-550 V DC
PV Isc16.9 A DC*2
Max. input current13.5 A DC*2
Rated output/input power6000/6000 W
Rated output apparent power6000 VA
Nominal voltage230 V AC
Rated input/output current27/27 A AC
Nominal frequency50 Hz
Power factor range0.8 leading to 0.8 lagging
EPS rated output apparent power4000 VA
EPS rated voltage230 V AC
EPS rated output current17.5 A AC
EPS nominal frequency50 Hz
Battery voltage range42-59 V DC
Rated charging/discharging current85 A DC
Type of batteryLithium/Lead-acid
Safety levelClass I
Overvoltage categoryPV: II, AC: III, Others: I
Ingress protectionIP65
Operation ambient temperature-25 C to +60 C
Inverter topologyNon-isolated
Certificate No.SAA211107

Frequently asked questions

What battery types can the JKS inverter use?

The JKS inverter can be used with lithium batteries or lead-acid batteries.

How long must I wait before opening the inverter after shutdown?

Wait 5 minutes before opening the upper lid or DC lid because residual voltage remains in the inverter.

What is the ingress protection rating?

The inverter has an ingress protection rating of IP65.

What is the service hotline?

The service hotline is +61 1300 326 182.