Sfere CD195X-9C7 Multi-loop Temperature Display Controller User Manual

The CD195X-9C7 is an 8‑channel temperature display controller with programmable relays, transmitter outputs and RS485 communication, detailed in this user…


Sfere CD195X-9C7 Multi-loop Temperature Display Controller User Manual - cover page
Brand
江苏斯菲尔电气
Category
Other
Document type
User Manual
Language
Chinese
Pages
13
File format
PDF
File size
485 KB
Updated
03 October, 2026
MD5 checksum
5B0B652D699DE65DDABF7DD8BD5E14E4

About this manual

This Chinese user manual covers the CD195X-9C7 multi-loop temperature display controller from Jiangsu Sfere Electric. According to the introduction, the instrument uses a dedicated microprocessor and a high-precision analog-to-digital converter with a modular hardware design, and it measures, displays and controls 8 channels of temperature signals. Typical applications named in the text are measuring the temperature of spindles and windings inside small and medium motors, where it gives alarm and trip signals, and monitoring the operating temperature of small and medium transformers.

The manual opens with the model selection table (96×96 mm housing, relay output, transmitter output, communication output and supply options), then lists the main electrical performance: analog inputs configurable per channel for Pt100, PTC/NTC, thermocouples J, K, B, R, S, T, E and N, and voltage or current signals; relay, 4–20 mA/0–20 mA transmitter and isolated RS485 Modbus outputs. The rest explains the front panel and measurement display state, how to switch into programming mode with the original password 0000, signal input programming for CH.1 to CH.8, relay alarm programming, communication and transmitter output programming, special functions, password change, system calibration and testing, a summary of programming parameters, dimensions and wiring, and a programming menu flowchart. This manual is written in Chinese.

What's inside

  • Product Introduction
  • Model Selection
  • Main Electrical Performance
  • Front Panel Description
  • Measurement Display State
  • Switching from Measurement to Programming State
  • Signal Input Programming (CH.1–CH.8)
  • Relay Alarm Output Programming
  • RS485 Communication Output Programming
  • Transmitter Output Programming

Specifications

Input channels8 analog input channels, each configurable independently
RTD inputPt100, -200 °C to +600 °C
Linear resistance input0–400 Ω range and 0–10 kΩ range (PTC/NTC)
Thermocouple inputJ, K, B, R, S, T, E, N
Current input0–20 mA / 4–20 mA (external 10 Ω precision resistor required)
Relay output2 normally closed relays or up to 4 normally open relays; contact rating AC250/5A or DC30V/5A
Transmitter output1 channel 4–20 mA / 0–20 mA
Communication outputRS485, optically isolated, standard Modbus protocol, baud rate 1200–9600 selectable internally
Measurement accuracy0.5%FS ±1 digit
Sampling periodRTD/PTC/NTC: 500 ms per channel; other signals: 200 ms per channel
DisplayTwo rows of 0.5/0.36 inch high-brightness LED digits; measured value -1999 to 9999
Supply voltageSwitching power supply AC/DC 80 V–270 V or AC/DC 18 V–32 V
Housing size96×96 mm

Frequently asked questions

What is the original password for entering the programming mode?

The instrument's original password is 0000; if the entered password is wrong the instrument returns to the measurement state.

How do I switch from the measurement state to the programming state?

In the measurement state press and hold the 返回 key for more than 3 seconds until the display shows PrOG, then press 确认 to enter the password.

What does the display show when a temperature sensor is open?

The first row of digits shows "r U P t" instead of a measured value; the manual says to power off and check the temperature sensor and its wiring.

Which communication protocol does the CD195X-9C7 use?

It uses standard Modbus-RTU over an optically isolated RS485 interface, with data read by 03 (or 04) commands.

How many temperature channels can the instrument measure?

It handles 8 channels of temperature signals, measured, displayed and controlled, with each channel configured independently.

Download PDF (485 KB)

More 江苏斯菲尔电气 Manuals


View all 江苏斯菲尔电气 manuals →