IVT IVT-1260/2460 Generator Auxiliary Excitation Device Operation Manual

Operation manual for the IVT-1260/2460 generator auxiliary excitation device, detailing specifications, installation, wiring, and usage procedures.


IVT IVT-1260/2460 Generator Auxiliary Excitation Device Operation Manual - cover page
Brand
IVT
Category
Generator
Document type
User Manual
Language
English
Pages
6
File format
PDF
File size
434 KB
Published
12 November, 2026
Updated
12 November, 2026
MD5 checksum
171C15B82168728003E3219B1AE1A605

About this manual

The IVT-1260/2460 is an auxiliary excitation device designed to boost motor starting capacity in shunt generators. It achieves this by converting DC battery power to an AC source for the Automatic Voltage Regulator (AVR), allowing the generator to handle larger motor starting currents. The device is easy to install and integrates quickly into generator excitation systems.

What's inside

  • Specification
  • Outer shape / Dimensions
  • Description
  • Auxiliary Boost Power Starting Procedure
  • Wiring Connections

Specifications

Input Measurement Voltage80 - 600 Vac (Single phase)
Transient Max. Power500 VA
Response Time10ms
Operating Temperature-40 - +70 ˚C
Storage Temperature-40 - +85 ˚C
Battery Power Input (IVT-1260)12 Vdc (10 - 14 Vdc) / 60A
Battery Power Input (IVT-2460)24 Vdc (20 - 28 Vdc) / 30A

Frequently asked questions

What is the maximum auxiliary output power of the IVT-1260/2460?

The highest auxiliary output power is 500VA.

What happens if the battery voltage is outside the specified range?

The Red LED turns on and the boost functions stop.

Can the IVT-1260/2460 be combined with an auxiliary power AVR?

Yes, but the AVR must use IGBT for excitation control method.