International Ceilcote 282 Flakeline Phenolic Vinyl Ester Lining System Data Sheet

Ceilcote 282 Flakeline is a two-component phenolic vinyl ester lining system with glass flake filler, designed for corrosion protection in flue gas…


International Ceilcote 282 Flakeline Phenolic Vinyl Ester Lining System Data Sheet - cover page
Brand
International
Category
Other
Document type
Product Leaflet
Language
Chinese
Pages
4
File format
PDF
File size
513 KB
Published
21 October, 2026
Updated
21 October, 2026
MD5 checksum
D42FA16EDB3040EF8107935A65361D9E

About this manual

Ceilcote 282 Flakeline is a two-component phenolic vinyl ester lining system filled with glass flakes. It is specifically designed for corrosion protection in flue gas desulfurization (FGD) environments. Typical applications include GGH equipment (hot and cold sides), absorber outlet pipework, steel chimneys/flues, and unscrubbed/unpurified gas transfer pipework. It is also suitable for continuous immersion in seawater absorption towers and as a film coating under inorganic, glass, brick, and tile linings.

The system is supplied as two components: Part A (base) and Part B (hardener). It is designed for application via airless spray, roller, or brush. The product has a high volume solids content of 85% and a dry film thickness range of 375-625 microns (15-25 mils). It is not intended as a decorative topcoat and is difficult to achieve color stability. This manual is written in Chinese.

What's inside

  • Product Description
  • Design Purpose
  • Coating Data
  • Surface Preparation
  • Mixing and Application
  • Drying Times
  • System Compatibility
  • Storage and Handling
  • Safety Precautions
  • Packaging Specifications

Specifications

Volume Solids85%
Dry Film Thickness375-625 microns (15-25 mils)
Wet Film Thickness441-735 microns (17.6-29.4 mils)
Theoretical Coverage (18 mils)76 sq ft/gal
Max Continuous Dry Temperature204°C (400°F)
Storage Life (Part A & B separate)6 months at 20°C
Mixing Ratio1 liter Part A : 20ml Part B

Frequently asked questions

What are the typical applications for Ceilcote 282 Flakeline?

It is suitable for GGH equipment, absorber outlet pipework, steel chimneys/flues, and unscrubbed/unpurified gas transfer pipework.

What is the recommended mixing ratio for the system?

The recommended ratio is 1 liter of Part A to 20ml of Part B.

What is the maximum continuous dry temperature the coating can withstand?

The coating can withstand a maximum continuous dry temperature of 204°C (400°F).

What is the recommended storage temperature for the product?

The recommended storage temperature range is 8°C to 19°C (46°F to 66°F).