Manual for the Ingenu IG1603/IG8150 fire broadcast telephone integrated system, covering features, specifications, wiring, debugging, and operation.
The system consists of the IG1603 fire telephone system and the IG8150 fire emergency broadcast system. The IG1603 system uses two-wire communication and includes the IG1603 fire telephone master, IG3602A/IG3602B fire telephone extensions, and IG5901 fire telephone jacks; the IG8150 host consists of a regional control panel, audio source equipment, and a broadcast power amplifier. The system is designed in accordance with GB16806-2006 and related amendment requirements.
The manual describes telephone and broadcast features, main parameters for each unit, wiring and terminal requirements, startup and debugging, telephone and broadcast operation, recording and event records, and password-protected settings. This manual is written in Chinese.
| Operating environment | Ambient temperature 0 to 40 C; relative humidity up to 95% RH |
|---|---|
| Telephone bus | Two-wire, polarity-independent; addresses 1 to 126 with no duplicates |
| IG1603 master dimensions | 318.0 x 245.0 x 129.5 mm |
| IG1603 master installation | Wall-mounted |
| IG1603 communication distance | 2000 m |
| IG1603 output voltage | 30 V / 36 V |
| IG1603 current | 60 mA |
| IG1603 voice frequency | 300 to 3400 Hz (+/-3 dB) |
| IG1603 transmission attenuation | Up to 5 dB |
| IG1603 call recording | Up to 24 minutes |
| IG1603 event records | 999 |
| IG1603 simultaneous calls | Up to 5 extensions |
| IG3602A/IG3602B dimensions | 201.5 x 44.4 x 41.5 mm |
| IG3602A/IG3602B standby current | 500 uA (typical) |
| IG3602A/IG3602B off-hook current | 30 mA |
| IG5901 dimensions | 86.0 x 86.0 x 31.5 mm |
| IG5901 standby current | 20 uA (typical) |
| IG8150 dimensions | 318.0 x 245.0 x 127.0 mm |
| IG8150 output voltage | Constant voltage 120 VAC |
| IG8150 recording duration | 30 minutes |
| IG8150 main power input | AC 187 to 242 V |
| IG8150 frequency response | 80 to 8000 Hz (+/-3 dB) |
| IG8150 signal-to-noise ratio | At least 70 dB |
| IG8150 backup power input | AC 187 to 242 V |
| IG8150 rated output | 1.25 A / 150 W |
| Broadcast output power | 150 W with natural cooling |
| Broadcast modes | Emergency broadcast with two audio sources, microphone, USB, and external line |
The default first-level password is 1111 and the second-level password is 2222.
The master can call up to five extensions simultaneously.
The telephone bus communication distance is 2000 meters.
The IG8150 has a rated output of 1.25 A / 150 W.