Indelac SNS4-15 Electric Actuator Installation Operation and Maintenance Manual

Installation, operation and maintenance guide for Indelac SNS4-15 electric actuators with internal battery backup.


Indelac SNS4-15 Electric Actuator Installation Operation and Maintenance Manual - cover page
Brand
Indelac
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
20
File format
PDF
File size
2.1 MB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
0C76EF5F2E1730BD23091E0F5AAB02EC

About this manual

This manual provides step-by-step instructions for installing, operating, and maintaining the Indelac SNS4-15 electric actuator. It covers mechanical mounting, electrical connections, fail-safe configuration, and maintenance procedures. The actuator features internal battery backup for uninterrupted operation during power failures and can be configured for fail-open, fail-close, or continuous run modes.

The device supports multiple voltage inputs (115vac, 230vac, 24vac, 24vdc, 12vdc) and includes position indication, feedback lamps, and optional modulating control for precise valve positioning. Proper wiring and setup are critical to ensure safe and reliable operation. This manual is written in Chinese.

What's inside

  • Introduction
  • Storage and Record Keeping
  • Tools Required
  • Product Description
  • Mechanical Mounting
  • Customer Electrical Connections
  • Actuator Setup for Standard Open/Close
  • Maintenance and Safety

Specifications

Enclosure RatingNEMA 4 Standard; 4X, 7 & 4/7 also available
Motor Duty Cycle100% Standard
Locked Rotor Current4.2 Amps
Full Load Amps1.8 Amps
Weight18 Lbs.
Mounting PadISO 5211 F07
Operating Voltages115vac, 230vac, 24vac, 24vdc, 12vdc
Battery12vdc, 0.8AHr
Battery Recharge TimeApproximately 8 Hours
Battery Life on Trickle Charge4-5 years
Auxiliary Switch RatingDry Contact, 15 Amps @ 125vac
Feedback Indicator Lamps12vdc @ 100mA max.
Input Signal Contact Rating12vdc @ 3A

Frequently asked questions

What is the battery backup feature of the SNS4-15 actuator?

The actuator has an internal battery that provides power to the motor in case of external power failure. It can be configured for fail-open, fail-close, or continuous run modes.

What are the available operating voltages for the SNS4-15 actuator?

The actuator supports 115vac, 230vac, 24vac, 24vdc, and 12vdc.

How do I configure the fail-safe mode?

Move the “Fail Switch” to the desired position: RUN (continue running), OPEN (move to open), or CLOSE (move to close).

What is the battery life on trickle charge?

The battery lasts approximately 4-5 years on trickle charge.

Download PDF (2.1 MB)