Installation, operation and maintenance guide for Indelac SNS4-15 electric actuators with internal battery backup.
This manual provides step-by-step instructions for installing, operating, and maintaining the Indelac SNS4-15 electric actuator. It covers mechanical mounting, electrical connections, fail-safe configuration, and maintenance procedures. The actuator features internal battery backup for uninterrupted operation during power failures and can be configured for fail-open, fail-close, or continuous run modes.
The device supports multiple voltage inputs (115vac, 230vac, 24vac, 24vdc, 12vdc) and includes position indication, feedback lamps, and optional modulating control for precise valve positioning. Proper wiring and setup are critical to ensure safe and reliable operation. This manual is written in Chinese.
| Enclosure Rating | NEMA 4 Standard; 4X, 7 & 4/7 also available |
|---|---|
| Motor Duty Cycle | 100% Standard |
| Locked Rotor Current | 4.2 Amps |
| Full Load Amps | 1.8 Amps |
| Weight | 18 Lbs. |
| Mounting Pad | ISO 5211 F07 |
| Operating Voltages | 115vac, 230vac, 24vac, 24vdc, 12vdc |
| Battery | 12vdc, 0.8AHr |
| Battery Recharge Time | Approximately 8 Hours |
| Battery Life on Trickle Charge | 4-5 years |
| Auxiliary Switch Rating | Dry Contact, 15 Amps @ 125vac |
| Feedback Indicator Lamps | 12vdc @ 100mA max. |
| Input Signal Contact Rating | 12vdc @ 3A |
The actuator has an internal battery that provides power to the motor in case of external power failure. It can be configured for fail-open, fail-close, or continuous run modes.
The actuator supports 115vac, 230vac, 24vac, 24vdc, and 12vdc.
Move the “Fail Switch” to the desired position: RUN (continue running), OPEN (move to open), or CLOSE (move to close).
The battery lasts approximately 4-5 years on trickle charge.