Hytork Twin Port Actuators (0-90°) & QA Series Installation, Operating and Maintenance Instructions

Hytork Twin Port Actuators (0-90°) & QA Series installation, operating and maintenance instructions covering safety, repair kits, disassembly, assembly…


Hytork Twin Port Actuators (0-90°) & QA Series Installation, Operating and Maintenance Instructions - cover page
Brand
Hytork
Category
Automation control Equipment
Document type
Service Manual
Language
English
Pages
4
File format
PDF
File size
78 KB
Published
16 November, 2026
Updated
16 November, 2026
MD5 checksum
9CC1553DAE141B07645DA0D011956D8C

About this manual

This is Hytork's Installation, Operating and Maintenance Instructions for Twin Port Actuators (0-90°) and the QA Series, document MAC129916. It starts with important safety procedures: disconnect air and electrical supplies before maintenance, isolate piping and relieve trapped media pressure before removing a valve, contain spring tension with Hytork Retractor Rods on spring return actuators, and never blow pistons out with air pressure when end caps are removed.

The document lists the contents of Hytork actuator repair kits, gives complete disassembly and assembly instructions for double acting and spring return models, refers to Fig. 5 for piping, and describes testing with compressed air at 80-100 psi (5.5 - 7 bar). It also covers cycling and testing actuators that have been stored or not operated for at least a 3 month period, and gives Hytork service contact details in the USA, Australia and the UK.

What's inside

  • Important Safety Procedures
  • Repair Kits
  • Complete Disassembly
  • Double Acting Models
  • Spring Return Models
  • Assembly Instructions
  • Piping Instructions
  • Testing the HYTORK Actuator
  • Testing and Cycling of Infrequently Used or Stored Actuators
  • Service

Specifications

Rotation range0–90°
Overtravel1.5 degrees at either end of the stroke
Travel stop adjustment10 degrees including overtravel
Test air pressure80-100 psi (5.5 - 7 bar)
Retractor rod thread engagementat least 1/2 in (12 mm)

Frequently asked questions

What must be done before carrying out maintenance on a Hytork actuator?

Disconnect the air and electrical supplies first; if a valve is being removed, isolate the piping system and relieve trapped media pressure.

How is spring tension contained during maintenance?

It is contained with Hytork Retractor Rods, as shown in the spring return end cap assembly figure.

What air pressure is used when testing the Hytork actuator?

Use compressed air at 80-100 psi (5.5 - 7 bar) and check the seal areas with soapy water for leaks.

How many times should stored actuators be cycled?

Actuators not operated for at least a 3 month period should be cycled a minimum of ten times.