HEX XL4 OCS Specifications and Installation Manual

This manual provides specifications and installation instructions for the HEX XL4 OCS controller, covering models HE-XC1E0 through HE-XC1E6 and HEXT 251C100…


HEX XL4 OCS Specifications and Installation Manual - cover page
Brand
HEX
Category
Industrial Robot
Document type
User Manual
Language
Chinese
Pages
10
File format
PDF
File size
1.8 MB
Published
21 October, 2026
Updated
21 October, 2026
MD5 checksum
E76F6A2C37F6AE0BFAAC09779D2BAF28

About this manual

This document serves as the specifications and installation guide for the HEX XL4 OCS programmable controller. It details the technical specifications, including logic performance, power requirements, and I/O capabilities for various supported models. The manual also covers external interface specifications such as the touchscreen, serial ports, USB, CAN, and Ethernet connections.

The guide provides comprehensive installation instructions, including safety precautions, terminal definitions for power, CAN, and serial ports, and DIP switch configurations. It further describes the built-in I/O boards (types 102, 103, 104, 105, and 106), explaining their specific channel counts, supported functions like high-speed counting and analog measurement, and wiring configurations for positive and negative logic. This manual is written in Chinese.

What's inside

  • Specifications
  • External Interface Specifications
  • Safety Precautions
  • Built-in I/O Boards
  • I/O Board Types
  • Wiring Specifications
  • Terminal Definitions
  • DIP Switch Settings
  • Ethernet Port
  • Technical Support

Specifications

Logic Language SupportAdvanced Ladder Diagram, IEC 61131-3
Power Requirement (Steady State)95 mA @ 24VDC, 190 mA @ 12VDC
Voltage Allowable Range10-30VDC
Screen ResolutionQVGA (320x240)
Ethernet Speed10/100Mbps
High-Speed Counter Max Frequency500KHz
Relay Output Max Current (Single Channel)3A
Operating Temperature-10℃ to +60℃

Frequently asked questions

What are the supported models for this manual?

The manual applies to models HE-XC1E0, HE-XC1E2, HE-XC1E3, HE-XC1E4, HE-XC1E5, HE-XC1E6, HEXT 251C100, HEXT 251C112, HEXT 251C113, HEXT 251C114, HEXT 251C115, and HEXT 251C116.

What is the maximum frequency for the high-speed counter?

The maximum frequency for the high-speed counter is 500KHz.

What is the allowable voltage range for the controller?

The allowable voltage range is 10-30VDC.

What is the maximum current for a single relay output channel?

The maximum current for a single relay output channel is 3A.