Hans Turck IMX12-DI03-1S-1NAM1T-0/24VDC/CC Isolated Switch Amplifier Datasheet

Hans Turck IMX12-DI03-1S-1NAM1T-0/24VDC/CC one-channel isolated switch amplifier for NAMUR sensors with SIL 2 and Zone 2 use.


Hans Turck IMX12-DI03-1S-1NAM1T-0/24VDC/CC Isolated Switch Amplifier Datasheet - cover page
Brand
Hans Turck
Category
Other Electronics
Document type
Product Leaflet
Language
Chinese
Pages
4
File format
PDF
File size
278 KB
Published
14 November, 2026
Updated
14 November, 2026
MD5 checksum
9B82FF6A1990835D30FAE7E123AAA2BE

About this manual

Hans Turck IMX12-DI03-1S-1NAM1T-0/24VDC/CC is a one-channel isolated switch amplifier for NAMUR sensors or passive couplers conforming to EN 60947-5-6. It has an intrinsically safe input circuit for use in Zone 2 and a transistor output, with switchable open-circuit and short-circuit monitoring.

The unit provides full galvanic isolation, reverse-polarity protection on the input, and removable spring-clamp terminals. It is rated SIL 2 according to IEC 61508 and carries ATEX, IECEx and other approvals; mechanical data include IP20 protection and an operating temperature range of -25 to +70 °C. This manual is written in Chinese.

What's inside

  • NAMUR input
  • Output circuits
  • Current isolation
  • Explosion protection
  • SIL safety circuit
  • Display/controls
  • Mechanical data
  • Environmental conditions
  • Standards
  • Accessories

Specifications

Model / order numberIMX12-DI03-1S-1NAM1T-0/24VDC/CC; order no. 7580006
Nominal operating voltage24 VDC
Operating voltage range10…30 VDC
Typical power loss≤ 1.03 W
NAMUR input open-circuit voltage8.2 VDC
NAMUR input short-circuit current8.2 mA
Input resistance1 kΩ
Cable resistance≤ 50 Ω
Switching threshold on1.75 mA
Switching threshold off1.55 mA
Wire breakage threshold≤ 0.06 mA
Short-circuit threshold≥ 6.4 mA
Transistor output switching voltage≤ 30 VDC
Transistor output switching current≤ 0.1 A
Switching frequency≤ 10000 Hz
Voltage drop≤ 2.7 V
Test voltage2.5 kV RMS
Protection ratingIP20
Flammability ratingV-0 (UL 94)
Operating temperature-25…+70 °C
Storage temperature-40…+80 °C
Dimensions120 x 12.5 x 128 mm
Weight153 g
Terminal cross-section0.2…2.5 mm² (AWG 24…14)
Maximum operating altitudeNot more than 2000 m above sea level
Pollution degreeII
SIL ratingSIL 2 according to IEC 61508
ATEX certificateTÜV 14 ATEX 147004 X

Frequently asked questions

What sensors can be connected to this amplifier?

NAMUR sensors or passive couplers conforming to EN 60947-5-6.

Can the device be used in hazardous areas?

Yes, it can be used in Zone 2.

Is input line monitoring available?

Yes, open-circuit and short-circuit monitoring of the input circuit can be switched on or off.

What is the SIL rating?

SIL 2 according to IEC 61508.

Download PDF (278 KB)