Greenheck FSJ-402 Stationary Louver Product Leaflet

Greenheck FSJ-402 is a galvanized steel stationary J-blade louver with 4 in. (102 mm) depth, size limits, wind load, free area, and AMCA-certified…


Greenheck FSJ-402 Stationary Louver Product Leaflet - cover page
Brand
Greenheck
Category
Other products
Document type
Product Leaflet
Language
English
Pages
3
File format
PDF
File size
404 KB
Published
19 November, 2026
Updated
19 November, 2026
MD5 checksum
24F16AD24813CD068C6E90D1BBCE020B

About this manual

Greenheck FSJ-402 is a stationary louver with J-style blades made of galvanized steel and a 4 in. (102 mm) depth. This leaflet lists construction details, minimum and maximum section sizes, wind load, free area, and AMCA-certified air performance and water penetration ratings.

It also includes a free area chart plus airflow resistance and water penetration data for a 48 in. x 48 in. (1219 mm x 1219 mm) test size, along with available options and accessories.

What's inside

  • Standard Details
  • Performance Ratings
  • Free Area Chart
  • Airflow Resistance
  • Water Penetration
  • Options and Accessories

Specifications

Frame material and wall thicknessGalvanized steel, 4 in. (102 mm) x 16 gauge
Blade style and thicknessJ Style, 20 gauge galvanized
Blade angle and spacing45º on approximately 4 in. (102 mm) centers
Louver depth4 in. (102 mm)
ConstructionMechanically fastened
FinishMill
Minimum size12 in. W x 12 in. H (305 mm W x 305 mm H)
Maximum single section size60 in. W x 96 in. H (1524 mm W x 2438 mm H)
Wind load25 PSF (1.2 kPa)
Free area7.55 sq. ft. (0.701 sq. m)
Percent free area47.2%
Free area velocity at beginning point of water penetration839 fpm (4.262 m/s)
Max intake volume at beginning point of water penetration6334 cfm (2.990 m³/s)
Intake pressure drop at 6,000 CFM0.095 in. wg (0.024 kPa)
CertificationAMCA Seal; AMCA Certified Ratings Program

Frequently asked questions

What is the maximum single section size of the FSJ-402 louver?

The maximum single section size is 60 in. W x 96 in. H (1524 mm W x 2438 mm H).

What wind load is specified for the FSJ-402 louver?

The specified wind load is 25 PSF (1.2 kPa).

What is the free area percentage of the FSJ-402 louver?

The free area percentage is 47.2%.

Is the FSJ-402 louver AMCA certified?

Greenheck Fan Corporation certifies that the FSJ-402 louvers shown are licensed to bear the AMCA Seal.