This manual provides installation, operation, and maintenance instructions for the GNB Marathon FTX 12V valve regulated lead acid stationary battery.
The GNB Marathon FTX is a 12 volt, valve regulated lead acid (VRLA) stationary battery designed for energy storage applications. Personnel handling, installing, operating, and maintaining this device must review all safety precautions before unpacking.
| Voltage | 12 volt |
|---|---|
| Chemistry | Valve regulated lead acid (VRLA) |
| Recommended Float Voltage (77°F) | 2.25 to 2.30 Volts Per Cell |
| Maximum Recharge Current (M12V155FTX) | 54 amps |
| Maximum Recharge Current (M12V180FTX) | 63 amps |
Batteries should be stored indoors in a cool, clean, and dry location, ideally at 25°C (77°F).
The recommended float voltage range is 2.25 to 2.30 Volts Per Cell (VPC).