GL GL-11E Static Inverse-Time Overcurrent Relay User Manual

User manual for the GL GL-11E static inverse-time overcurrent relay, covering technical parameters, wiring, and setting methods for motor and transformer…


GL GL-11E Static Inverse-Time Overcurrent Relay User Manual - cover page
Brand
G&L
Category
Other Electronics
Document type
User Manual
Language
Chinese
Pages
3
File format
PDF
File size
160 KB
Published
10 November, 2026
Updated
10 November, 2026
MD5 checksum
1F49A2172307AE576E0C5DBB331F4799

About this manual

This manual describes the GL-11E series static inverse-time overcurrent relay, designed for use in motor, transformer, and power distribution systems, particularly in stations without DC auxiliary power. Key features include the ability to operate reliably during overloads and short circuits, high anti-interference capability, and the absence of mechanical jamming found in electromagnetic relays. It can replace older models such as the GL-11, GL-12, GL-15, DL-10, DL-20, and DL-30 series. This manual is written in Chinese.

What's inside

  • Overview
  • Main Technical Parameters
  • Inverse-Time Delay Characteristics
  • Terminal Wiring
  • Setting Methods

Specifications

Overcurrent setting range1-9.9A
Instantaneous current multiple1-9.9 times
Delay time setting range0.1-9.9
Contact capacityAC250V, 5A continuous
Power consumptionNot more than 5W
Operating temperature-10°C ~+50°C
Dielectric strength2000V AC, 1 minute
Insulation resistanceNot less than 300MΩ
Electrical life100000 times

Frequently asked questions

What is the overcurrent setting range for the GL-11E?

The overcurrent setting range is 1-9.9A with a step of 0.1A.

Can the GL-11E replace older electromagnetic relays?

Yes, it can replace GL-11, GL-12, GL-15, DL-10, DL-20, and DL-30 series current relays.

Does the GL-11E require DC auxiliary power?

No, it does not require DC auxiliary power.