About this manual

The GE Multilin T35 is a three-phase transformer protection relay intended for power transformers of any rating with up to 6 windings/brakes. It is a member of the UR series of relays and can be used alone or as one element in a substation automation system, providing both primary and backup protection for power transformers and autotransformers.

The leaflet describes the protection and control functions, including restrained and unrestrained (instantaneous) differential protection with a dual-slope, dual-knee restraint characteristic, second- and fifth-harmonic restraint, and backup overcurrent protection. It also covers metering and measurement, oscillography, event and data recording, the front-panel local HMI with programmable LEDs and buttons, the multi-language interface, communication protocols such as IEC 61850 and Modbus, and multi-breaker bus configurations. This manual is written in Chinese.

What's inside

  • 保护和控制
  • 比例差动保护
  • 谐波涌流制动
  • 过激磁制动
  • 瞬时差动
  • 后备保护
  • 监视与测量
  • 录波与事件记录
  • 用户接口及编程
  • 多断路器配置

Specifications

Transformer windings/brakesUp to 6
Digital inputs and outputsUp to 80 digital inputs and 50 digital outputs
Event records1024 time-tagged events
Digital input scan time0.5 ms
Data logging channelsUp to 16 channels, user-programmable sample rate
Oscillography channelsUp to 64
Oscillography sampling rateUp to 64 samples per cycle
Fault records stored in relay64
Programmable LEDs48 user-programmable LEDs
Communication protocolsIEC 61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC 60870-5-104, EGD

Frequently asked questions

How many transformer windings can the T35 protect?

The T35 protects power transformers with up to 6 windings/brakes, of any rating.

Which communication protocols does the T35 support?

The leaflet lists IEC 61850, DNP 3.0 Level 2, Modbus RTU, Modbus TCP/IP, IEC 60870-5-104 and Ethernet Global Data (EGD).

How many events does the event recorder keep?

It captures the most recent 1024 time-tagged events with a 0.5 ms digital input scan time.

Does the T35 interface support Chinese?

Yes, French, Chinese and Russian options are provided for the local display, front panel, EnerVista setup software and instruction manual.