GD RS: 018/00 FGD Bypass Bi-Plane Damper Specification

Technical specification for the GD RS: 018/00 FGD Bypass Bi-Plane Damper used in Wet Lime Stone FGD systems for flue gas diversion.


GD RS: 018/00 FGD Bypass Bi-Plane Damper Specification - cover page
Brand
G&D
Category
Other
Document type
User Manual
Language
English
Pages
89
File format
PDF
File size
5 MB
Published
22 November, 2026
Updated
22 November, 2026
MD5 checksum
0369FE92C979202CE497D4164C2DEA75

About this manual

The GD RS: 018/00 is a Bi-plane damper located between the ID fan and chimney, designed to divert flue gas into an FGD plant for sulphur removal treatment. It features a twin blade louver design with two plates mounted to single shaft trunnions and reinforced with stiffeners.

What's inside

  • Project Information
  • Application
  • Scope of supply
  • Working Environment
  • Operational Requirement
  • Design Criteria
  • Construction Details
  • Material of Construction
  • Seal Air system
  • Actuator System for Damper

Specifications

Duct inner dimensions6000mm width x 12007 mm height
Ambient temperature (Guarantee)27 Deg C
Compressed air pressure4.5 kg/cm2 (max)
Duct cross section area72.042 m2

Frequently asked questions

What is the purpose of the Bi-plane damper?

It is used for diverting the flue gas into the FGD plant for sulphur removal treatment instead of allowing it directly into the chimney.

How is the damper operated during normal closing?

It closes in three steps (40%, 40%, and 20%) via 4-20mA signals from the DCS to maintain boiler pressure.

What is the requirement for emergency opening?

The actuator must open the damper completely from full close to full open within an adjustable time of 10 to 20 seconds.