Frese ELCO-100 Local Controller Quick Guide

Frese ELCO-100 local controller quick guide: wiring a PT100 sensor or 4–20 mA transmitter and setting inputs, outputs, control mode and PI parameters.


Frese ELCO-100 Local Controller Quick Guide - cover page
Brand
Frese
Category
Automation control Equipment
Document type
Quick Start Guide
Language
English
Pages
9
File format
PDF
File size
1.2 MB
Published
09 November, 2026
Updated
09 November, 2026
MD5 checksum
14C15E86D30F679E6EAC0694EC3A0AFE

About this manual

This quick guide from Frese describes setting up the standalone ELCO-100 local controller. It shows the back-terminal wiring for a 3-wire PT100 sensor and for a 4–20 mA current-loop transmitter (0 to 100 °C) with a 24 VDC power supply, and identifies the front keys used to move through the menus.

The guide is built around worked menu examples: setting the analog input to 4…20 mA or to a 3-wire RTD probe with Pt100 linearization, selecting a 3-point step or continuous control type, setting the analog output to 4…20 mA, choosing control direction for heating or cooling, changing the PI controller parameters (Xp1, Tn1 and actuator time TT), and setting the serial interface address, baud rate and data format. A closing table lists 90° running times for 3-point actuators, followed by Frese office contact details.

What's inside

  • Application example 1: Set analog Input type: 4…20mA
  • Application example 2: Set analog Input type: 3w RTD temp. probe
  • Application example 3: Set control type
  • Application example 4: Set analog output: 4…20mA
  • Application example 5: Setup control for heating/cooling applications
  • Application example 6: Change PI-controller parameters
  • Setup BUS communication
  • Recommended PI-controller setup
  • Actuator running time

Specifications

Analog input signal type4…20 mA or 3-wire RTD (Pt100)
Analog output signal type4…20 mA
Recommended proportional band Xp140 (lower to e.g. 30 if correction is too slow)
Recommended reset time Tn1300 seconds; never lower than 100 seconds
Serial interface baud rate9600
Serial interface data format8-1-even parity
Running time 90°, actuator 58-893617 s at 50 Hz / 14 s at 60 Hz

Frequently asked questions

Which Frese temperature sensors fit the 4…20 mA input setting?

The guide lists types 58-8965, 58-8966, 58-8967 and 58-8968 for the 4…20 mA setting.

How do I set the input for a 3-wire RTD temperature probe?

In Configuration, open Analog input, change the signal type to 3w RTD temp probe, then set Linearization to Pt100.

How is the controller set up for cooling instead of heating?

Under Controller config, set Control direction to Direct for cooling; Inverse is the other setting described.

What are the recommended PI controller values?

A proportional band Xp1 of around 40 and a reset time Tn1 of around 300 seconds are recommended.