Installation manual for the EVAX 25/50/100/150/200 Voice Evacuation System, covering wiring, power, batteries and terminal connections.
The EVAX 25/50/100/150/200 Voice Evacuation Interface System is a self-contained amplifier, tone generator, digital message repeater and supervisory interface designed for use with a UL listed Fire Alarm Control Panel (FACP) to provide a listed voice evacuation alarm system. It provides internal supervision and speaker-line supervision, with faults reported back to the FACP.
This installation manual covers the model configurations, installation and wiring, power and battery connections, and terminal designations. It gives requirements for speaker lines, FACP signaling circuits, EOLR connections and accessory cards, and states that all terminals are power limited and should be wired in accordance with NFPA 70, NFPA 101 and NFPA 72.
| Primary power | 120 VAC at 60 Hz |
|---|---|
| Speaker line voltage | 25 or 70 Vrms (jumper selected; 25 V factory set) |
| EVAX 25 speaker output | 25 W to the speaker circuit |
| Minimum battery size | 24V 7Ah |
| Maximum battery size housed in cabinet | 12Ah |
| FACP signal circuit input | 10 mA max. |
| TB1 power input | 24–32 V AC/DC |
It is a self-contained amplifier, tone generator, digital message repeater and supervisory interface used with a UL listed FACP to provide a voice evacuation alarm system.
The EVAX 25/50/100 is designed to be powered from 120 VAC at 60 Hz; models may also be supplied with transformers wired for 240 VAC where required.
Speakers may be 25 or 70 Vrms; 25 V is the factory setting.
The minimum battery size is 24V 7Ah.