Installation manual for the Evapco PMC-E CHJV 125D high velocity evaporative condenser, covering lifting, assembly, and structural support.
This document is an installation guide for the Evapco PMC-E series high velocity evaporative condensers. It provides detailed instructions on transportation, storage precautions, general safety rules, and compliance with international building codes (IBC). The manual outlines specific requirements for steel structure supports to ensure proper load distribution during operation. This manual is written in Chinese.
| Maximum beam deflection limit | 1/360 of length and not exceeding 1/2" (13mm) |
|---|---|
| Maximum beam tilt limit | Less than 1.5mm per meter |
The beam's curvature must not exceed one-third of its length or 13mm.
Units with a length greater than 6m require either 6 or 8 lifting points.
The minimum height H for lifting this unit's water pan/fan section is 3.6 meters.