Product labels and technical specifications for the GNExCP6 series of explosion-proof manual call points, including voltage ratings and environmental limits.
This document provides product labels and technical specifications for the GNExCP6 series of manual call points manufactured by European Safety Systems Ltd. The series includes models designated as GNExCP6A, GNExCP6B, GNExCP6C, GNExCP6D, and GNExCP6E, each with specific nominal voltage ratings.
The document details the electrical ratings, including maximum AC and DC voltages and corresponding current limits for resistive and inductive loads. It also specifies the operating temperature ranges and explosion protection ratings (ATEX and IECEx) for each model variant.
| Product Type | Manual Call Point |
|---|---|
| Manufacturer | European Safety Systems Ltd. |
| IP Rating | IP66 |
| Operating Temperature Range (Model A) | -40ºC to +70ºC |
| Operating Temperature Range (Model B) | -40ºC to +50ºC |
| Operating Temperature Range (Model C) | -40ºC to +65ºC |
| Operating Temperature Range (Model D) | -40ºC to +70ºC |
| Operating Temperature Range (Model E) | -40ºC to +65ºC |
| Max AC Voltage (Model A) | 250V |
| Max DC Voltage (Model A) | 75V |
| Explosion Rating (Model A) | 2GD Ex db eb IIC T6 Gb |
| Explosion Rating (Model B) | 2GD Ex db eb mb IIC T4 Gb |
| Explosion Rating (Model C) | 2GD Ex db eb mb IIC T4 Gb |
| Explosion Rating (Model D) | 2GD Ex db eb mb IIC T4 Gb |
| Explosion Rating (Model E) | 2GD Ex db eb mb IIC T4 Gb |
Clean only with a damp cloth to avoid electrostatic hazards.
No, the unit must not be opened when an explosive atmosphere may be present.
The GNExCP6B-PT model is available with nominal voltages of 48V DC, 24V DC, 12V DC, and 6V DC.