User manual for the EUCHNER ESM-BA2.. emergency stop safety relay, covering installation, commissioning, wiring diagrams, and technical specifications.
This document serves as the user information for the EUCHNER ESM-BA2.. emergency stop safety switching device. It details the correct use, features, and functions of the device, which is designed for safe isolation of safety circuits according to DIN EN 60204-1. The manual supports applications up to safety category 4 and Performance Level e (PL e) according to DIN EN ISO 13849-1.
| Performance Level | PL e |
|---|---|
| Safety Category | Category 4 |
| Operating Voltage | AC/DC 24V, AC 115V, AC 230V |
| Supply Frequency | 50-60Hz |
| Control Current | approx. 40 mA |
| Safety Contacts | 2 NO contacts |
| Max. Switching Voltage (AC) | AC 250 V |
| Breaking Capacity (AC) | 250 V, 1500 VA, 6 A for ohmic load |
| Breaking Capacity (DC) | 24 V, 144 W, 6 A for ohmic load |
| Contact Material | AgSnO2 |
| Contact Service Life | approx. 1 x 10^7 |
| Test Voltage | 2.5 kV |
| Rated Impulse Withstand Voltage | 4 kV |
| Rated Insulation Voltage | 250 V |
| Degree of Protection | IP20 |
| Temperature Range (DC 24V) | -15°C to +60°C |
| Temperature Range (AC) | -15°C to +40°C |
| Mounting | DIN rail according to EN 60715TH35 |
| Weight | approx. 230 g |
The device is designed for use up to safety category 4.
The device is certified up to a Performance Level of PL e.
The device must be checked once per month for proper function and signs of tampering.
It is mounted on a 35-mm DIN rail according to DIN EN 60715 TH35.