EUCHNER ESM-BA2.. Emergency Stop Safety Relay User Manual

User manual for the EUCHNER ESM-BA2.. emergency stop safety relay, covering installation, commissioning, wiring diagrams, and technical specifications.


EUCHNER ESM-BA2.. Emergency Stop Safety Relay User Manual - cover page
Brand
EUCHNER
Category
Industrial Supply
Document type
User Manual
Language
English
Pages
4
File format
PDF
File size
1.1 MB
Published
05 November, 2026
Updated
05 November, 2026
MD5 checksum
18FBEBF4A6DA8B633BDA3F21A2FDCE02

About this manual

This document serves as the user information for the EUCHNER ESM-BA2.. emergency stop safety switching device. It details the correct use, features, and functions of the device, which is designed for safe isolation of safety circuits according to DIN EN 60204-1. The manual supports applications up to safety category 4 and Performance Level e (PL e) according to DIN EN ISO 13849-1.

What's inside

  • User Information
  • Correct Use
  • Features
  • Function
  • Electrical Connection
  • Installation
  • Safety Precautions
  • Commissioning Procedure
  • Maintenance
  • Techn. Data

Specifications

Performance LevelPL e
Safety CategoryCategory 4
Operating VoltageAC/DC 24V, AC 115V, AC 230V
Supply Frequency50-60Hz
Control Currentapprox. 40 mA
Safety Contacts2 NO contacts
Max. Switching Voltage (AC)AC 250 V
Breaking Capacity (AC)250 V, 1500 VA, 6 A for ohmic load
Breaking Capacity (DC)24 V, 144 W, 6 A for ohmic load
Contact MaterialAgSnO2
Contact Service Lifeapprox. 1 x 10^7
Test Voltage2.5 kV
Rated Impulse Withstand Voltage4 kV
Rated Insulation Voltage250 V
Degree of ProtectionIP20
Temperature Range (DC 24V)-15°C to +60°C
Temperature Range (AC)-15°C to +40°C
MountingDIN rail according to EN 60715TH35
Weightapprox. 230 g

Frequently asked questions

What is the maximum safety category supported by the ESM-BA2..?

The device is designed for use up to safety category 4.

What is the maximum Performance Level (PL) for this device?

The device is certified up to a Performance Level of PL e.

How often must the device be checked for maintenance?

The device must be checked once per month for proper function and signs of tampering.

What type of mounting is required for the ESM-BA2..?

It is mounted on a 35-mm DIN rail according to DIN EN 60715 TH35.