A quick start guide for configuring the HMS Gateway Anybus Communicator with Emotron MSF 2.0 and VFX/FDU 2.0 drives as Modbus-RTU masters.
This document provides step-by-step instructions for configuring the HMS Gateway Anybus Communicator to work with Emotron MSF 2.0 soft starters and VFX/FDU 2.0 variable frequency drives. It details how to set up the gateway as a Modbus-RTU master and map process data registers between the fieldbus and the drive networks.
The guide covers specific configuration steps for both MSF 2.0 and VFX/FDU 2.0 products, including setting baud rates, slave addresses, and transaction data. It also includes a network comparison chart explaining byte swapping requirements for different network protocols like Profibus, Ethernet/IP, and Modbus RTU.
This guide covers the Emotron MSF 2.0 soft starter and the Emotron VFX/FDU 2.0 variable frequency drives.
The manual configuration mode is recommended because the wizard does not allow byte swapping.
You can alter the update time by marking the Query to the left and changing the Update time value to the right.