User manual for the Emerson Network Power APM 300 integrated UPS single module and parallel system, covering safety, installation, operation modes, battery…
This user manual covers the Emerson Network Power APM 300 integrated UPS in single-module and parallel-system configurations. It is intended for trained engineers approved and qualified by the manufacturer or its agent, and addresses safety precautions, installation, operation, battery management, and product specifications.
The manual includes system design and bypass information, parallel system requirements, operation modes, battery management and protection, mechanical and electrical installation notes, environmental and mechanical characteristics, and conformity information.
| Rated power | 30, 60, 90, 120, 150, 180, 210, 240, 270, 300 kVA |
|---|---|
| Noise within 1 m (front) | 56 to 65 dB depending on rated power |
| Altitude | Up to 1000 m; derate power by 1% per 100 m between 1000 m and 2000 m |
| Relative humidity | 20 to 90 %RH, non-condensing |
| Operating temperature | 0 to 40 °C |
| Storage and transport temperature | -25 to +55 °C |
| Recommended battery storage temperature | -20 to +30 °C |
| Main/switch cabinet dimensions | 600 × 1100 × 2000 mm |
| Power module dimensions | 440 × 598 × 173 mm |
| Weight | 150 kg (main cabinet), 180 kg (switch cabinet), 34 kg (power module) |
| Protection degree | IP20 |
| Conformity standards | CE 2006/95/EC and 93/68/EEC, 2004/108/EC, C-Tick, IEC62040-1, IEC62040-2, IEC62040-3 |
Yes. It must be commissioned and serviced by trained engineers approved and qualified by the manufacturer or its agent.
No. It is designed for commercial and industrial use only and is not for use in any life support application.
The operating temperature range is 0 to 40 °C, and battery life is halved for every 10 °C increase above 20 °C.
The switch cabinet has IP20 protection with the front door open or closed and the back door closed.