Installation instructions for EHK electric heater kits EHK05A, EHK08A, EHK10A, EHK15B and EHK20B used in air handlers.
These installation instructions cover EHK electric heater kits for use in air handlers, including models EHK05A, EHK08A, EHK10A, EHK15B and EHK20B. The document gives safety cautions, installation steps, wiring notes and kit descriptions.
The text lists heat strip ratings from 5kW to 20kW and MCA/MOP data for air handler models. It also states that a W1/W2 signal energizes the electric heater and indoor blower, with a 90-second blower off delay.
| EHK05A(UL) heat strip | 5kW |
|---|---|
| EHK08A(UL) heat strip | 7.5kW |
| EHK10A(UL) heat strip | 10kW |
| EHK15B(UL) heat strip | 15kW; double breaker's panel |
| EHK20B(UL) heat strip | 20kW; double breaker's panel |
All power must be disconnected before installation. The cautions note that there may be more than one disconnect servicing the unit.
Use copper conductors only.
When the indoor control board receives a W1/W2 signal, the electric heater is energized and the indoor blower is turned on.
Check all breaker screws and make sure they are properly tight.