Installation and operation guide for Dingxin Electric's 150kW/187.5kVA generator set with engine specs, control systems, and fuel requirements.
This manual provides installation and operational instructions for the Dingxin Electric DVD165 PrimePower(50Hz) generator set. It details engine specifications, control systems, fuel and cooling requirements, and optional accessories. The generator is rated for 150kW/187.5kVA standby power and 165kW/206.3kVA prime power, with a Vovlo Penta TAD732GE engine and ComAp control system.
The manual includes technical parameters such as voltage, frequency, fuel consumption, noise levels, and dimensions. It also covers safety features, monitoring capabilities, and optional components like ATS systems, mufflers, and filters for different applications. This manual is written in Chinese.
| Rated Voltage | 400/230 V |
|---|---|
| Rated Current | 270/297 A |
| Rated Frequency | 50 Hz |
| Power Factor | 0.8 (lagging) |
| Rated Speed | 1500 r/min |
| Fuel Specification | O# light diesel |
| Noise Value | <105dB at 1m |
| Genset Dimension (Open Type) | 2550x866x1600 mm |
| Net Weight (Open Type) | 1500 kg |
| Engine Displacement | 7.15 L |
| Maximum Output Power | 183 kW |
| Coolant Capacity | 23.8 L |
| Maximum Coolant Temperature | 113°C |
| Oil Consumption Rate | 0.08 L/h |
| Voltage Adjustment Range | 95~105% |
| Frequency Adjustment Rate (Stable) | 1% |
| Voltage Fluctuation Rate | +1% |
| Frequency Fluctuation Rate | 0.5% |
| Control System | ComAp NT MRS 10 |
| Protection Grade | IP23 |
| Insulation Class | H |
The rated power is 150kW/187.5kVA for standby and 165kW/206.3kVA for prime power.
The generator uses a Vovlo Penta TAD732GE engine with turbocharged, aftercooled aspiration.
The control system is ComAp NT MRS 10, supporting electronic control engines and remote/local monitoring.
The fuel consumption rate is 213 g/kWh for prime power and 214 g/kWh for standby power.