Installation guide for the Dell PowerConnect W-6000 fan tray (HW-FT), covering features, LED status indicators, and hot-swap replacement steps.
This document is the installation guide for the fan tray (HW-FT) of the Dell PowerConnect W-6000 controller chassis. The fan tray provides cooling for the W-6000M3 module and is required for normal operation; the W-6000 chassis operating temperature range is 0 to 40 °C (32 to 104 °F), and the software raises warnings when temperature thresholds are exceeded. The guide describes the tray's general and physical features, including built-in redundancy (three independent fans), hot-swapping, the tray slot location, and the status LED indications.
It then gives step-by-step instructions for replacing the fan tray: preparing the new tray, loosening the captive screws, separating and removing the old tray, inserting and seating the new one, and securing it. Because the W-6000 has no shutdown function, a hot-swap replacement must be completed within one minute; if two or more fans fail (amber/red LED), the chassis must be shut down and cooled before restart. The document closes with safety and regulatory notices (FCC Part 15, Canadian ICES-003), Dell support links, and copyright/legal statements noting the product is sourced from Aruba Networks. This manual is written in Chinese.
| Chassis operating temperature | 0 to 40 °C (32 to 104 °F) |
|---|---|
| Minor temperature alarm | 40 °C |
| Major temperature alarm | 50 °C |
| Critical temperature alarm | 60 °C |
| Fans per tray | 3 independent fans |
| Hot-swap time limit | 1 minute |
| Fan tray slot location | Left side of the W-6000 chassis, extending from front to back |
An amber LED means one fan has failed, but the remaining two fans can still provide adequate cooling until the fan tray is replaced.
Shut down the W-6000, replace the fan tray, let the chassis cool for at least five minutes, then power it back on.