About this manual

The Daikin EKRTR room thermostat controls Daikin systems for radiator heating and floor heating/cooling applications. It can be wall-mounted or used as a table-top model, and the optional EKRTETS sensor can be connected as an external ambient or floor temperature sensor.

The manual covers installation of the thermostat and receiver, code setup in the installer menu, and technical characteristics for the thermostat, receiver and optional sensor.

What's inside

  • Introduction
  • Installation of EKRTETS as floor temperature sensor
  • Installation of the EKRTR
  • Wall-mounted installation
  • Table-top installation of the thermostat
  • Installation of the receiver
  • Setting up codes in the installer menu
  • Technical characteristics
  • Miscellaneous codes

Specifications

Temperature readoutSteps of 0.1°C/0.1°F
Operating temperature (thermostat)0°C~50°C/32°F~122°F
Setpoint temperature range4°C~37°C in steps of 0.5°C; 39.5°F~99°F in steps of 0.5°F
Electrical protection (thermostat)Class II - IP30 (indoor use, polution degree 2)
Feeding and autonomy3 alkaline batteries AA.LR6 1.5 V, approximately 2 years
Electrical protection (receiver)Class II - IP44 (indoor use, polution degree 2)
Power supply (receiver)1N~50 Hz 230 VAC
Radio frequency433.92 MHz, <10 mW
Rangeapproximately 100 m in open space; approximately 30 m in residential environment
Output relays maximum load4 A - 230 VAC
Maximum fuse amp3 A
Power consumption15 W, maximum
Immunity against voltage surgesCategory III (2.5 kV)
Type of automatic action1C
External temperature sensorNTC 10K at 25°C/3 meter lead; NTC 10K at 77°F/3 meter lead

Frequently asked questions

What systems can the Daikin EKRTR control?

It can be used to control the Daikin system for radiator heating and floor heating/cooling applications.

When can the EKRTR be used as a table-top model?

Only if the optional EKRTETS temperature sensor is not installed as an external temperature sensor.

What can the optional EKRTETS sensor be used for?

It can be used as an external ambient temperature sensor or as a floor temperature sensor for floor heating/cooling applications.

What batteries does the EKRTR thermostat use?

It uses 3 alkaline batteries AA.LR6 1.5 V, with autonomy of approximately 2 years depending on usage conditions.