Daikin ARUH36TLAV / ARUH48TLAV / ARUH60TLAV Duct Type Indoor Unit Installation Manual

Installation manual for Daikin ARUH36TLAV, ARUH48TLAV and ARUH60TLAV duct type VRF indoor units: piping, drain work, wiring and field settings.


Daikin ARUH36TLAV / ARUH48TLAV / ARUH60TLAV Duct Type Indoor Unit Installation Manual - cover page
Brand
Daikin
Category
Air conditioner
Document type
Installation Guide
Language
English
Pages
15
File format
PDF
File size
2.1 MB
Published
17 November, 2026
Updated
17 November, 2026
MD5 checksum
588076AD3331D3712D5F71BC14931B69

About this manual

This is the installation manual (PART NO. 9373870135-03) for Daikin VRF system indoor units of the duct type, models ARUH36TLAV, ARUH48TLAV and ARUH60TLAV. It is intended for authorized service personnel only and covers safety precautions, installation work, refrigerant pipe installation, drain piping, electrical wiring, field settings, test run, a check list and error codes.

The manual opens with general and special precautions, including notes on R410A refrigerant, the dedicated tools and piping materials required for it, and the accessories furnished with the unit. It then describes selecting an installation location, pipe and flare connection work, heat insulation, drain pipe installation, electrical requirements and wiring methods, external input/output and remote sensor options, address and function settings, test run using the outdoor unit PCB or the remote controller, and final checks.

What's inside

  • Safety Precautions
  • About This Product
  • Precautions for using R410A refrigerant
  • Special tool for R410A
  • Accessories
  • Installation Work
  • Pipe Installation
  • Installing Drain Pipes
  • Electrical Wiring
  • Field Setting

Specifications

RefrigerantR410A
Drain hose sizeΦ 3/4 in. (19 mm) I.D., Φ 1-1/16 in. (27 mm) O.D.
R410A charging port thread1/2 UNF, 20 threads per inch
Gauge manifold high pressure display range30 in.Hg to 768 psi (–0.1 to 5.3 MPa)
Gauge manifold low pressure display range30 in.Hg to 551 psi (–0.1 to 3.8 MPa)
Vacuum pump capacity5 Torr, –755 mmHg (–100.7 kPa)
R410A working pressure compared with R22Approximately 1.6 times higher

Frequently asked questions

What refrigerant does this indoor unit use?

The unit uses R410A refrigerant, which requires dedicated tools and piping materials made for R410A.

How long must I wait after turning off the power before touching electrical components?

Wait 5 minutes or more after turning off the power before touching electrical components.

Can a conventional R22 vacuum pump be used for R410A?

Yes, a conventional (R22) vacuum pump can be used by installing a vacuum pump adapter.

Who is allowed to install the unit?

The manual is for authorized service personnel only, and installation should be requested from a dealer or professional installer.

Download PDF (2.1 MB)

More Daikin Manuals


View all Daikin manuals →