Installation manual for Daikin ARUH36TLAV, ARUH48TLAV and ARUH60TLAV duct type VRF indoor units: piping, drain work, wiring and field settings.
This is the installation manual (PART NO. 9373870135-03) for Daikin VRF system indoor units of the duct type, models ARUH36TLAV, ARUH48TLAV and ARUH60TLAV. It is intended for authorized service personnel only and covers safety precautions, installation work, refrigerant pipe installation, drain piping, electrical wiring, field settings, test run, a check list and error codes.
The manual opens with general and special precautions, including notes on R410A refrigerant, the dedicated tools and piping materials required for it, and the accessories furnished with the unit. It then describes selecting an installation location, pipe and flare connection work, heat insulation, drain pipe installation, electrical requirements and wiring methods, external input/output and remote sensor options, address and function settings, test run using the outdoor unit PCB or the remote controller, and final checks.
| Refrigerant | R410A |
|---|---|
| Drain hose size | Φ 3/4 in. (19 mm) I.D., Φ 1-1/16 in. (27 mm) O.D. |
| R410A charging port thread | 1/2 UNF, 20 threads per inch |
| Gauge manifold high pressure display range | 30 in.Hg to 768 psi (–0.1 to 5.3 MPa) |
| Gauge manifold low pressure display range | 30 in.Hg to 551 psi (–0.1 to 3.8 MPa) |
| Vacuum pump capacity | 5 Torr, –755 mmHg (–100.7 kPa) |
| R410A working pressure compared with R22 | Approximately 1.6 times higher |
The unit uses R410A refrigerant, which requires dedicated tools and piping materials made for R410A.
Wait 5 minutes or more after turning off the power before touching electrical components.
Yes, a conventional (R22) vacuum pump can be used by installing a vacuum pump adapter.
The manual is for authorized service personnel only, and installation should be requested from a dealer or professional installer.