User guide for Control Solutions BB2-3010 and BB2-3060 BACnet-Modbus gateways, covering configuration, tools, troubleshooting, and hardware details.
Control Solutions BB2-3010 and BB2-3060 are BACnet-Modbus gateways: BB2-3010 connects BACnet MS/TP to Modbus RTU, while BB2-3060 connects BACnet MS/TP to Modbus TCP. The guide explains gateway functions, configuration methods, and the configuration tool pages.
It also includes troubleshooting appendices for Modbus and BACnet, CSV and XML file formats, USB driver installation, and hardware details such as wiring and LED indicators.
| BB2-3010 gateway type | BACnet MS/TP to Modbus RTU gateway |
|---|---|
| BB2-3060 gateway type | BACnet MS/TP to Modbus TCP gateway |
| Microprocessors | BB2-3010 has one 32-bit ARM7; BB2-3060 has two |
| Configuration network | MS/TP network |
| Configuration access | BACnet object properties |
| BB2-3010 Modbus role | Modbus RTU master or slave, not both at the same time |
| BB2-3060 Modbus role | Both Modbus TCP master and slave at the same time |
| Default BACnet role | Server (slave) |
| Connection via router | BACnet IP to MS/TP router |
| Connection via adapter | MTX002 USB to MS/TP adapter |
The BB2-3010 is a BACnet MS/TP to Modbus RTU gateway, while the BB2-3060 is a BACnet MS/TP to Modbus TCP gateway.
All configuration is done via the MS/TP network.
No, it can be configured as a Modbus RTU master or slave, but never both at the same time.
It can connect via the Control Solutions MTX002 USB to MS/TP adapter.