The Chint DZ20L residual current circuit breaker provides leakage protection for 380‑400 V AC networks up to 630 A, with optional phase‑loss and…
The DZ20L series residual current circuit breaker is designed for 50 Hz AC distribution networks with rated voltages of 380 V or 400 V and currents up to 630 A. It protects against fire hazards caused by insulation failure, overload, short‑circuit, and ground‑fault currents, and can be used for both general distribution and motor protection.
Key features include optional phase‑loss protection that disconnects the circuit within 0.2 s, a transparent polycarbonate cover for visual contact status, and a leak‑alarm module that can be added for uninterrupted‑power‑supply environments. The series complies with GB/T 14048.2 and IEC 60947‑2 standards and offers various configurations such as four‑pole or three‑pole‑four‑wire, with or without delay, and adjustable residual‑current settings. This manual is written in Chinese.
| Number of Poles | 4 (four‑pole) or 3N (three‑pole four‑wire) |
|---|---|
| Rated Residual Operating Current (I△n) | 30 mA – 500 mA (selectable) |
| Rated Residual Making Capacity (I△m) | 3 kA – 5 kA |
| Insulation Voltage (Ui) | 800 V (660 V for some models) |
| Arc Distance | 6 mm – 10 mm |
A transparent‑cover version is available, using a high‑temperature polycarbonate material that allows visual checking of the contacts.
The DZ20L complies with GB/T 14048.2 and IEC 60947‑2 standards.