BTI AWAX28XXL Electromechanical Safety Module User Manual

User manual for the BTI AWAX28XXL electromechanical safety module, covering installation, operation modes, wiring diagrams, and technical specifications for…


BTI AWAX28XXL Electromechanical Safety Module User Manual - cover page
Brand
BTI
Category
Industrial Supply
Document type
User Manual
Language
French
Pages
4
File format
PDF
File size
737 KB
Published
19 October, 2026
Updated
19 October, 2026
MD5 checksum
CDAFD4AF30B684E1D145E6E0D9C97372

About this manual

This document serves as the user manual and conformity declaration for the BTI AWAX28XXL electromechanical safety module. The device is designed to monitor mechanical switches, ACOTOM sensors, or emergency stop push buttons with at least two normally closed (NC) lines. It features nine safety outputs (eight normally open and one normally closed) and complies with safety standards such as EN ISO 13849 and EN 62061. This manual is written in French.

What's inside

  • Domaine d'application
  • Instructions de montage
  • Fonctionnement
  • Sélection du mode de réarmement
  • LED de visualisation
  • Caractéristiques techniques
  • Préconisations
  • Câblage

Specifications

Switching Capacity (AC1)8A/250V
Switching Capacity (AC15)5A/250V
Switching Capacity (DC13)5A/24V
Power Supply24 VDC +/-15%
Ambient Temperature-20 °C / +60 °C
Dimensions45 x 100 x 111mm
Protection ClassIP20
Performance LevelPL e
Safety Category4 or SIL3

Frequently asked questions

What is the recommended test interval for the safety outputs?

It is recommended to test the system at least once a year.

What is the maximum diameter of the wiring cable?

The maximum diameter of the wiring cable is 2.08 mm² (14 AWG).

What fuse is advised for the power supply input?

It is advised to install a 400 mA fuse between A1 and the power supply.

What fuse is advised for each safety output line?

It is advised to install an 8 A fuse on each safety output line.