User manual for the BTI AWAX28XXL electromechanical safety module, covering installation, operation modes, wiring diagrams, and technical specifications for…
This document serves as the user manual and conformity declaration for the BTI AWAX28XXL electromechanical safety module. The device is designed to monitor mechanical switches, ACOTOM sensors, or emergency stop push buttons with at least two normally closed (NC) lines. It features nine safety outputs (eight normally open and one normally closed) and complies with safety standards such as EN ISO 13849 and EN 62061. This manual is written in French.
| Switching Capacity (AC1) | 8A/250V |
|---|---|
| Switching Capacity (AC15) | 5A/250V |
| Switching Capacity (DC13) | 5A/24V |
| Power Supply | 24 VDC +/-15% |
| Ambient Temperature | -20 °C / +60 °C |
| Dimensions | 45 x 100 x 111mm |
| Protection Class | IP20 |
| Performance Level | PL e |
| Safety Category | 4 or SIL3 |
It is recommended to test the system at least once a year.
The maximum diameter of the wiring cable is 2.08 mm² (14 AWG).
It is advised to install a 400 mA fuse between A1 and the power supply.
It is advised to install an 8 A fuse on each safety output line.