Installation and operation manual for the Broseley York Midi gas stove, covering assembly, flue and gas connections, coal layout, and servicing.
The Broseley York Midi is a gas-fired radiant convector stove designed to run on either natural gas or LPG, with non-interchangeable burner units for the two gas types. The manual provides technical information, dimensions, siting requirements, assembly steps, flue and gas connection guidance, pressure testing, coal layout, operating instructions, and servicing information.
It states that installation must comply with national regulations and be carried out by a qualified and accredited gas fitter on the Gas Safe register. It also covers ventilation, spillage testing, troubleshooting, and the guarantee, and lists specifications including heat input, supply pressure, dimensions, and weight.
| Heat input (gross), natural gas | 6.2 Kw/Hr |
|---|---|
| Gas rate, natural gas | 0.59 M3/Hr |
| Width | 457 mm (18 in) |
| Weight excluding optional canopy | 65 kg (143 lbs) |
| Maximum heat output (approx.) | 4.6 kilowatts |
| Flue spigot diameter | 127 mm (5 in) |
| Minimum hearth thickness | 12 mm |
| Gas supply connection pipe | 8 mm semi-rigid, max 1 m |
The York Midi is designed to run on either natural gas or LPG. The burner units are not interchangeable between the two gas types.
Installation, assembly and commissioning must be carried out by a professionally qualified and accredited gas fitter listed on the Gas Safe register. The manual says not to install the appliance yourself.
For natural gas, the pressure is 20 mbar measured at the burner test nipple with the appliance at full rate.
The flue must have a minimum height of 3 metres to ensure adequate draught.