Bosch DKM 2014/2, DM 1103 B-Ex Fire Alarm Systems - Conventional Manual Call Points for Ex Areas

User manual for Bosch DKM 2014/2 and DM 1103 B-Ex manual call points designed for explosive zones 1 and 2.


Bosch DKM 2014/2, DM 1103 B-Ex Fire Alarm Systems - Conventional Manual Call Points for Ex Areas - cover page
Brand
Bosch
Document type
User Manual
Language
English
Pages
3
File format
PDF
File size
382 KB
Published
06 November, 2026
Updated
06 November, 2026
MD5 checksum
1FE1F53D53F5D1543A395FE716FCB8F2

About this manual

This document details the installation, operation, and technical specifications of Bosch’s DKM 2014/2 and DM 1103 B-Ex manual call points for use in explosive areas. It includes wiring and safety barrier requirements, certifications, and physical specifications. The devices are designed for manual alarm activation in hazardous zones and feature weatherproof housings with specific mounting and reset procedures.

Installation guidelines specify mounting height, location along escape routes, and compliance with VdS/VDE standards. Technical specs cover operating voltage, contact type, cable entry, housing material, dimensions, weight, protection class, temperature range, and explosion-proof classification for each model.

What's inside

  • Functions
  • Certifications and Approvals
  • Installation/Configuration Notes
  • Technical Specifications
  • Ordering Information
  • Accessories

Specifications

Operating Voltage20 - 26.5 V DC
Switch Contact TypeType 366 (encapsulated), II 2 G EEx d II C
Maximum Contact Load5 A / 250 V AC 0,25 A / 250 V DC
Cable Entry1x M16 x 1.5 tightening diameter 4‑8 mm, EEx e II
Housing MaterialPolyester, glass fiber reinforced
ColorsRed, RAL 3001
Dimensions136 x 138 x 88 mm
WeightApprox. 1800 g
Protection ClassIP 66
Permissible Operating Temperature-25 °C to +40 °C
Ex ClassificationEex emd IIC T6
Operating Voltage16V DC to 28V DC
Housing MaterialPlastic, PC
ColorRed, RAL 3000
Dimensions134.4 x 134.4 x 43.5 mm
WeightApprox. 200 g
Protection ClassIP 54
Permissible Operating Temperature-25 °C to +60 °C
Permissible Storage Temperature-30 °C to +75 °C
Permissible Relative Humidity≤100% at T≤34 °C
Ex ClassificationEEx ib IIC T4
Input Voltage≤ 28 V
Input Current≤ 100 mA
Input Power≤ 700 mW
Internal Inductivity0 mH
Internal Capacitance0 nF

Frequently asked questions

What is the maximum contact load for the DKM 2014/2 manual call point?

Maximum contact load is 5 A / 250 V AC and 0.25 A / 250 V DC.

What is the protection class for the DKM 2014/2 manual call point?

Protection class is IP 66 as per EN 60529.

What is the permissible operating temperature range for the DM 1103 B-Ex manual call point?

Permissible operating temperature is -25 °C to +60 °C.

Download PDF (382 KB)

More Bosch Manuals